The BAPI BACnet IP Output Module (BA/BIP-BLE-EZ) converts data from up to 28 BAPI BLE wireless sensors into BACnet IP objects for direct integration into the BMS Ethernet network. BACnet IP is an open standard protocol, so this module works with any BACnet-compatible controller or BMS — no proprietary middleware required.
Best for: BAS integrators who need to bring BAPI BLE wireless sensor data directly into a BACnet IP network, eliminating the need for analog output modules when the BMS supports BACnet IP point integration.
Carries BAPI's 5-year warranty. The module auto-discovers all sensors paired to the receiver and creates BACnet objects automatically. Configuration is done through a standard web browser — no proprietary software needed once the module is on the network.
Auto-Discovery — No Manual Object Configuration
When connected to the BAPI BLE Receiver, the BACnet IP module automatically discovers all paired sensors and creates Analog Input and Binary Input BACnet objects for each measured variable. Object names and COV delta values can be customized through the web interface after discovery.
BACnet IP for Up to 28 Sensors
Integrates wireless sensor data directly into the BMS Ethernet backbone. Supports temperature, humidity, setpoint, contact status, battery level, and signal strength objects per sensor.
Web-Based Configuration
Accessible via any browser at the module's DHCP-assigned IP address. Default: UDP port 47808, username admin, password admin. No proprietary software or USB cables needed.
Lost Comm Fault Reporting
If a sensor does not transmit for 35 minutes, the BACnet Event State changes to Fault and Reliability shows Communication Failure. Reverts to Normal within 5 seconds of the next transmission.
Powered Through Receiver or Separately
Powers in-line through the BAPI BLE Receiver, or separately at 15 to 24 VDC using the BA/AOM-CONN kit for remote mounting.
| Specification | Value |
|---|---|
| Part Number | BA/BIP-BLE-EZ |
| Supply Power | 15 to 24 VDC or powered through receiver |
| Power Consumption | 40 mA max @ 24 VDC |
| Ethernet Standard | 10/100BASE-TX |
| BACnet UDP Port | 47808 (default) |
| Default Credentials | Username: admin / Password: admin |
| Lost Comm Timeout | 35 minutes |
| Operating Temp | 32 to 140°F (0 to 60°C) |
| Mounting | Surface, 2.75 in snaptrack, or 35mm DIN rail |
| Agency | RoHS (CE pending) |
| Warranty | 5 Years |
- Module Type:
- Digital Output Module
- Protocol:
- BACnet IP
- Sensor Capacity:
- Up to 28
- Interface:
- 10/100 Ethernet