The Belimo AHKX24-MFT-100 is a fail-safe linear damper actuator with 450 N [100 lbf] of actuating force and a 4" [100 mm] stroke. It runs on AC/DC 24 V nominal voltage with MFT/programmable control and a 2 to 10 V default operating range. It has a NEMA 2 degree of protection.
Specifications sourced from the Belimo AHKX24-MFT-100 technical data sheet (en-us, 2026-10-20).
Best for
- Damper control that needs 450 N [100 lbf] of linear actuating force over a 4" [100 mm] stroke
- Applications that require a fail-safe position on loss of power
- Jobs that need a programmable (MFT) control input
- Air plenum installations (UL 2043 compliant)
Key Features
450 N [100 lbf] Actuating Force
Motor actuating force of 450 N [100 lbf]. Stroke: 4" [100 mm].
Fail-Safe Operation
Fail-safe running time: <35 s. Direction of fail-safe motion: reversible with switch. Fail-safe position setting: adjustable with dial or tool 0 to 100% in 10% increments. Bridging time (PF): 2 s. Pre-charging time: 5 to 26 s.
MFT Programmable Control
Operating range Y: 2 to 10 V (4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)). Variable operating range: Start point 0.5 to 30 V End point 2.5 to 32 V. Optional operating modes: variable (VDC, on/off, floating point). Position feedback U: 2 to 10 V.
NEMA 2 Enclosure
Degree of protection NEMA/UL: NEMA 2. Housing: UL Enclosure Type 2. UL 2043 compliant: Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC.
Running Time and Override
Motor running time: 150 s / 100 mm. Variable running time: 90 to 150 s. Manual override: external push button.
ZOT Supply is an authorized distributor of Belimo products.
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Belimo |
| Part Number | AHKX24-MFT-100 |
| Nominal Voltage | AC/DC 24 V |
| Nominal Voltage Frequency | 50/60 Hz |
| Nominal Voltage Range | AC 19.2 to 28.8 V / DC 21.6 to 28.8 V |
| Power Consumption in Operation | 11 W |
| Power Consumption in Rest Position | 3 W |
| Transformer Sizing | 22 VA |
| Electrical Connection | 18 AWG appliance or plenum cables, 1 m, 3 m or 5 m, with or without 1/2" NPT conduit connector |
| Overload Protection | electronic throughout full stroke |
| Electrical Protection | actuators are double insulated |
| Actuating Force Motor | 450 N [100 lbf] |
| Operating Range Y | 2 to 10 V |
| Operating Range Y Note | 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor) |
| Input Impedance | 100 kΩ for 2 to 10 V (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, On/Off and Floating point |
| Operating Range Y Variable | Start point 0.5 to 30 V End point 2.5 to 32 V |
| Operating Modes Optional | variable (VDC, on/off, floating point) |
| Position Feedback U | 2 to 10 V |
| Position Feedback U Note | Max. 0.5 mA |
| Position Feedback U Variable | VDC variable |
| Setting Fail-Safe Position | adjustable with dial or tool 0 to 100% in 10% increments |
| Bridging Time (PF) | 2 s |
| Bridging Time (PF) Variable | 0 to 10 s |
| Pre-Charging Time | 5 to 26 s |
| Direction of Motion Motor | selectable with switch 0/1 |
| Direction of Motion Fail-Safe | reversible with switch |
| Manual Override | external push button |
| Stroke | 4" [100 mm] |
| Running Time (Motor) | 150 s / 100 mm |
| Running Time Motor Variable | 90 to 150 s |
| Running Time Fail-Safe | <35 s |
| Sound Power Level Motor | 52 dB(A) |
| Sound Power Level, Fail-Safe | 61 dB(A) |
| Adaptation Setting Range | off (default) |
| Override Control | MIN (minimum position) = 0% MID (intermediate position) = 50% MAX (maximum position) = 100% |
| Power Source UL | Class 2 Supply |
| Degree of Protection NEMA/UL | NEMA 2 |
| Housing | UL Enclosure Type 2 |
| Agency Listing | cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU |
| Quality Standard | ISO 9001 |
| UL 2043 Compliant | Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC |
| Ambient Humidity | Max. 95% RH, non-condensing |
| Ambient Temperature | -22 to 122°F [-30 to 50°C] |
| Storage Temperature | -40 to 176°F [-40 to 80°C] |
| Servicing | maintenance-free |
| Weight | 2.9 lb [1.3 kg] |
| Housing Material | UL94-5VA |
| Notes | Variable when configured with MFT options. Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3 |
| Warranty | 5 years |
Documentation
Related Options
Accessories
Tools
Electrical Accessories
Mechanical Accessories
Frequently Asked Questions
What is the Belimo AHKX24-MFT-100?
The Belimo AHKX24-MFT-100 is a fail-safe linear damper actuator with 450 N [100 lbf] of actuating force and a 4" [100 mm] stroke. It runs on AC/DC 24 V nominal voltage with MFT/programmable control and a 2 to 10 V default operating range. It has a NEMA 2 degree of protection.
What power supply does the AHKX24-MFT-100 need?
The AHKX24-MFT-100 has a nominal voltage of AC/DC 24 V at 50/60 Hz, with a nominal voltage range of AC 19.2 to 28.8 V / DC 21.6 to 28.8 V. Power consumption is 11 W in operation and 3 W in rest position. Transformer sizing: 22 VA.
What control signal does the AHKX24-MFT-100 use?
The AHKX24-MFT-100 uses MFT Programmable control. Operating range note: 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor). The operating range Y is 2 to 10 V. Input impedance: 100 kΩ for 2 to 10 V (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, On/Off and Floating point. Position feedback U: 2 to 10 V.
What force and stroke does the AHKX24-MFT-100 provide?
The AHKX24-MFT-100 delivers 450 N [100 lbf] of actuating force over a 4" [100 mm] stroke.
Is the AHKX24-MFT-100 a fail-safe actuator?
Yes. The AHKX24-MFT-100 is a fail-safe actuator with a fail-safe running time of <35 s. Direction of fail-safe motion: reversible with switch.
What is the running time of the AHKX24-MFT-100?
Motor running time is 150 s / 100 mm. Variable running time: 90 to 150 s.
What is the enclosure rating of the AHKX24-MFT-100?
The AHKX24-MFT-100 has a NEMA 2 degree of protection (UL Enclosure Type 2). UL 2043 compliant: Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC. Ambient temperature: -22 to 122°F [-30 to 50°C]. Ambient humidity: Max. 95% RH, non-condensing.
- Actuator Type:
- Fail-Safe
- Torque / Force:
- 100 lbf
- Stroke:
- 4 in
- Control Signal:
- Programmable (MFT)
- Voltage:
- 24 VAC/DC
- Auxiliary Switch:
- None
- Enclosure:
- NEMA 2
- Series:
- AH
- Feedback Signal:
- 2-10 VDC