Skip to main content

Functional Devices RIB01P30-NC : Enclosed Power Relay, 30 Amp Contact Rating, Relay Contact Type: DPST-N/C, 120 Vac Coil Voltage, NEMA 1 Housing

Functional Devices

MSRP: $226.60
$113.30
(You save $113.30 )
(No reviews yet) Write a Review
SKU:
RIB01P30-NC
Condition:
New
Availability:
6 In Stock | Ready to Ship
Adding to cart… The item has been added
Functional Devices RIB01P30-NC: Enclosed Power Relay, 30 Amp Contact Rating, Relay Contact Type: DPST-N/C, 120 Vac Coil Voltage, NEMA 1 Housing, Made in USA
Specifications
  • Relays & Contact Type: One (1) DPST Continuous Duty Coil – Normally Closed
  • Expected Relay Life: 10 million cycles minimum mechanical
  • Operating Temperature: -30 to 140° F
  • Humidity Range: 5 to 95% (noncondensing)
  • Operate Time: 18ms
  • Relay Status: LED On = Activated
  • Dimensions: 4.00" x 4.00" x 1.81" with 0.50" NPT Nipple
  • Wires: 16", 600V Rated
  • Approvals: UL Listed, UL916, UL864, C-UL, California State Fire Marshal, CE, RoHS
  • Housing Rating: Accepted for Use in Plenum, NEMA 1
  • Gold Flash: Yes
  • Override Switch: No
Contact Ratings:
  • 30 Amp Resistive @ 300 Vac
  • 25 Amp Resistive @ 28 Vdc
  • 20 Amp Ballast @ 277–480 Vac (Not rated for Electronic Ballast)
  • 15 Amp Resistive @ 600 Vac
  • 770 VA Pilot Duty @ 120 Vac
  • 1,158 VA Pilot Duty @ 240 Vac
  • 1,110 VA Pilot Duty @ 277 Vac
  • 1,640 VA Pilot Duty @ 480 Vac
  • Heavy Pilot Duty @ 600 Vac
  • 3 HP @ 480–600 Vac
  • 2 HP @ 240–277 Vac
  • 1 HP @ 120 Vac

Coil Current: 105 mA @ 120 Vac

Coil Voltage Input: 120 Vac; 50–60 Hz (Drop Out = 35 Vac, Pull In = 85 Vac)

Control Wiring: Wht/Blk = 120 Vac Continuous, Wht/Red = 120 Vac Control, Wht/Yel = Neutral

Frequently Asked Questions
  • What does DPST-N/C mean?
    DPST-N/C stands for Double Pole Single Throw – Normally Closed. This means both poles remain closed until the coil is energized, allowing current to pass through by default.
  • Is this relay rated for electronic ballasts or LED drivers?
    No. The RIB01P30-NC is not rated for electronic loads such as LED drivers or electronic ballasts. Use only with rated resistive or inductive loads.
  • How do I order different contact combinations?
    Add “-NONC” to the model number to get one pole normally open and one normally closed.
Installation Tips & Mistakes to Avoid
  • Tip: Use the -NC configuration when you need fail-safe circuits that default to “closed” when unpowered.
  • Tip: Always verify control wiring per the datasheet when using alternate contact configurations like -NC or -NONC.
  • Mistake to Avoid: This relay is not intended for switching LED or electronic ballast loads. Use a rated model for those applications.
Mounting:
Enclosed
Number of Relays:
1
Relay Contact Type:
DPDT
Relay Coil Voltage:
120 Vac
Contact Ratings:
30 Amp