Skip to main content

Functional Devices RIB01P30-NONC : Enclosed Power Relay, 30 Amp Contact Rating, Relay Contact Type: DPST-N/O/N/C, 120 Vac Coil Voltage, NEMA 1 Housing

Functional Devices

MSRP: $219.30
$109.65
(You save $109.65 )
(No reviews yet) Write a Review
SKU:
RIB01P30-NONC
Condition:
New
Availability:
0 In Stock | 3-5 Day Leadtime
Adding to cart… The item has been added
Functional Devices RIB01P30-NONC: Enclosed Power Relay, 30 Amp Contact Rating, Relay Contact Type: DPST-N/O/N/C, 120 Vac Coil Voltage, NEMA 1 Housing, Made in USA
Specifications
  • Relays & Contact Type: One (1) DPST Continuous Duty Coil – Pole 1 Normally Open / Pole 2 Normally Closed
  • Expected Relay Life: 10 million cycles minimum mechanical
  • Operating Temperature: -30 to 140° F
  • Humidity Range: 5 to 95% (noncondensing)
  • Operate Time: 18ms
  • Relay Status: LED On = Activated
  • Dimensions: 4.00" x 4.00" x 1.81" with 0.50" NPT Nipple
  • Wires: 16", 600V Rated
  • Approvals: UL Listed, UL916, UL864, C-UL, California State Fire Marshal, CE, RoHS
  • Housing Rating: Accepted for Use in Plenum, NEMA 1
  • Gold Flash: Yes
  • Override Switch: No
Contact Ratings:
  • 30 Amp Resistive @ 300 Vac
  • 25 Amp Resistive @ 28 Vdc
  • 20 Amp Ballast @ 277–480 Vac (Not rated for Electronic Ballast)
  • 15 Amp Resistive @ 600 Vac
  • 770 VA Pilot Duty @ 120 Vac
  • 1,158 VA Pilot Duty @ 240 Vac
  • 1,110 VA Pilot Duty @ 277 Vac
  • 1,640 VA Pilot Duty @ 480 Vac
  • Heavy Pilot Duty @ 600 Vac
  • 3 HP @ 480–600 Vac
  • 2 HP @ 240–277 Vac
  • 1 HP @ 120 Vac

Coil Current: 105 mA @ 120 Vac

Coil Voltage Input: 120 Vac; 50–60 Hz (Drop Out = 35 Vac, Pull In = 85 Vac)

Control Wiring: Wht/Blk = 120 Vac Continuous, Wht/Red = 120 Vac Control, Wht/Yel = Neutral

Frequently Asked Questions
  • What does DPST-N/O/N/C mean?
    This refers to a double-pole relay where one contact is normally open (N/O) and the other is normally closed (N/C). This provides control flexibility within a single relay.
  • How is this different from the standard RIB01P30?
    The standard RIB01P30 has both contacts normally open. The RIB01P30-NONC features mixed contact positions: Pole 1 is N/O, Pole 2 is N/C.
  • Can this be used with LED drivers or electronic ballasts?
    No. The relay is not rated for electronic ballast or LED driver loads. Use a model specifically rated for electronic loads.
Installation Tips & Mistakes to Avoid
  • Tip: Use the -NONC variant for applications needing both make and break contacts triggered from a single coil.
  • Tip: Carefully label pole wiring to reflect the mixed contact configuration during installation.
  • Mistake to Avoid: Never wire this relay assuming both poles are the same. One is N/O, one is N/C — wiring must reflect this.
  • Mistake to Avoid: Do not use for electronic ballast or LED drivers. This relay is not designed for high-inrush capacitive loads.
Mounting:
Enclosed
Number of Relays:
1
Relay Contact Type:
DPST-N/O/N/C
Relay Coil Voltage:
120 Vac
Contact Ratings:
30 Amp