Functional Devices RIB01P30-S-NONC: Enclosed Power Relay, 30 Amp Contact Rating, Relay Contact Type: DPST-N/O/N/C + Coil Side Override, 120 Vac Coil Voltage, NEMA 1 Housing, Made in USA
Specifications
- Relays & Contact Type: One (1) DPST Continuous Duty Coil – Pole 1 Normally Open / Pole 2 Normally Closed
- Expected Relay Life: 10 million cycles minimum mechanical
- Operating Temperature: -30 to 140° F
- Humidity Range: 5 to 95% (noncondensing)
- Operate Time: 18ms
- Relay Status: LED On = Activated
- Dimensions: 4.00" x 4.00" x 1.81" with 0.50" NPT Nipple
- Wires: 16", 600V Rated
- Approvals: UL Listed, UL916, UL864, C-UL, California State Fire Marshal, CE, RoHS
- Housing Rating: Accepted for Use in Plenum, NEMA 1
- Gold Flash: Yes
- Override Switch: Coil Side
- 30 Amp Resistive @ 300 Vac
- 25 Amp Resistive @ 28 Vdc
- 20 Amp Ballast @ 277–480 Vac (Not rated for Electronic Ballast)
- 15 Amp Resistive @ 600 Vac
- 770 VA Pilot Duty @ 120 Vac
- 1,158 VA Pilot Duty @ 240 Vac
- 1,110 VA Pilot Duty @ 277 Vac
- 1,640 VA Pilot Duty @ 480 Vac
- Heavy Pilot Duty @ 600 Vac
- 3 HP @ 480–600 Vac
- 2 HP @ 240–277 Vac
- 1 HP @ 120 Vac
Coil Current: 105 mA @ 120 Vac
Coil Voltage Input: 120 Vac; 50–60 Hz (Drop Out = 35 Vac, Pull In = 85 Vac)
Control Wiring: Wht/Blk = 120 Vac Continuous, Wht/Red = 120 Vac Control, Wht/Yel = Neutral
Frequently Asked Questions
- What does N/O/N/C mean?
This refers to a two-pole relay with one pole normally open (N/O) and the other normally closed (N/C). This configuration provides both make and break functions in a single device. - What makes the RIB01P30-S-NONC unique?
It combines split contact logic (N/O and N/C) with a coil-side override switch, ideal for systems needing dual signal behavior and manual testing capability. - Is this relay suitable for LED or electronic ballast loads?
No. This relay is not rated for electronic ballasts or LED drivers. Select an electronic load-rated model for those applications.
Installation Tips & Mistakes to Avoid
- Tip: Use clear labeling for each pole to avoid wiring mistakes. Mismatched N/O/N/C logic can cause system failure or unexpected operation.
- Tip: Use the coil-side override to test relay activation during commissioning.
- Mistake to Avoid: Don’t wire both poles assuming identical logic. One is normally open and one is normally closed by design.
- Mistake to Avoid: Avoid using this relay in LED lighting circuits or where high inrush current is present.
- Mounting:
- Enclosed
- Number of Relays:
- 1
- Relay Contact Type:
- DPST-N/O/N/C
- Relay Coil Voltage:
- 120 Vac
- Contact Ratings:
- 30 Amp