Functional Devices RIB01P30: Enclosed Power Relay, 30 Amp Contact Rating, Relay Contact Type: DPST-N/O, 120 Vac Coil Voltage, NEMA 1 Housing, Made in USA
Specifications
- Relays & Contact Type: One (1) DPST Continuous Duty Coil
- Expected Relay Life: 10 million cycles minimum mechanical
- Operating Temperature: -30 to 140° F
- Humidity Range: 5 to 95% (noncondensing)
- Operate Time: 18ms
- Relay Status: LED On = Activated
- Dimensions: 4.00" x 4.00" x 1.81" with 0.50" NPT Nipple
- Wires: 16", 600V Rated
- Approvals: UL Listed, UL916, UL864, C-UL, California State Fire Marshal, CE, RoHS
- Housing Rating: Accepted for Use in Plenum, NEMA 1
- Gold Flash: Yes
- Override Switch: No
- 30 Amp Resistive @ 300 Vac
- 25 Amp Resistive @ 28 Vdc
- 20 Amp Ballast @ 277–480 Vac (Not rated for Electronic Ballast)
- 15 Amp Resistive @ 600 Vac
- 770 VA Pilot Duty @ 120 Vac
- 1,158 VA Pilot Duty @ 240 Vac
- 1,110 VA Pilot Duty @ 277 Vac
- 1,640 VA Pilot Duty @ 480 Vac
- Heavy Pilot Duty @ 600 Vac
- 3 HP @ 480–600 Vac
- 2 HP @ 240–277 Vac
- 1 HP @ 120 Vac
Coil Current: 105 mA @ 120 Vac
Coil Voltage Input: 120 Vac; 50–60 Hz (Drop Out = 35 Vac, Pull In = 85 Vac)
Control Wiring: Wht/Blk = 120 Vac Continuous, Wht/Red = 120 Vac Control, Wht/Yel = Neutral
Frequently Asked Questions
- What does DPST-N/O mean?
DPST stands for Double Pole Single Throw. Both poles are normally open (N/O), meaning both circuits are closed only when the relay is energized. - Can the RIB01P30 handle electronic ballasts or LED loads?
No. The relay is not rated for electronic ballasts and should not be used with LED drivers. For these applications, select a relay rated for electronic loads. - Are alternate contact configurations available?
Yes. To order both poles as normally closed, add “-NC” to the model number. For mixed contact operation (Pole 1 N/O, Pole 2 N/C), add “-NONC”.
Installation Tips & Mistakes to Avoid
- Tip: Use the appropriate control lead configuration for either continuous or control-only activation, as listed in the wiring diagram.
- Tip: Mount in a dry, indoor location to maintain NEMA 1 housing compliance.
- Mistake to Avoid: This relay is not designed for electronic loads such as LED drivers or electronic ballasts.
Datasheets
![]() | Functional Devices RIB01P30 Specifications |
- Mounting:
- Enclosed
- Number of Relays:
- 1
- Relay Contact Type:
- DPST-N/O
- Relay Coil Voltage:
- 120 Vac
- Contact Ratings:
- 30 Amp