Functional Devices RIBM02ZNDC : Dry Contact Relay, 30 Amp DPDT, Class 2 Dry Contact Input, 208-277 Vac Power Input, 4.00" Track Mount
Product Features
- Prepackaged for quick and easy installation
- Provides low-voltage (Class2) power needed to activate the relay (self-powered) by closing the dry contact input
- Activated by a wide range of dry contacts such as thermostats, switches, other relays, solid-state switches, etc.
- Power to energize the relay can be brought to the relay on a separate pair of wires along with the control output of the controller, or can be a local power source near the relay
- Relay contacts are isolated from the input power and the dry contact input, so they can be wired to switch any other power-load or low-voltage load (see specifications for contact ratings)
SPECIFICATIONS
# Relays & Contact Type: One (1) DPDT Continuous Duty Coil
Expected Relay Life: 10 million cycles minimum mechanical
Operating Temperature: -30 to 140° F
Humidity Range: 5 to 95% (noncondensing)
Operate Time: 18ms
Relay Status: Red LED On = Activated
Power Status: Green LED On = Activated
Dimensions: 2.88”H x 4.00”W x 1.50”D1/2.00”D2
Track Mount: 4.000"
MT4 Mounting Track Sold Separately
Approvals: UL Component Recognized, UL916 C-UL, CE, RoHS
Gold Flash: Yes
Override Switch: No
Contact Ratings:
30 Amp Resistive @ 300Vac
25 Amp Resistive @ 28Vdc
15 Amp Resistive @ 600Vac
3 HP @ 480-600 Vac
2 HP @ 240/277 Vac
1 HP @ 120 Vac
20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
770VA @ 120Vac
1158VA @ 240Vac
1109VA @ 277Vac
1640VA @ 480Vac
NEMA B600 Pilot Duty
Power Input: 95 mA @ 208-277 Vac (RIBM01ZNDC)
Notes:
- Dry Contact Input Operation: Close dry contact to activate relay.
- If more than one dry contact input RIB shares a single dry contact input, DCI COM must be common.
Data Sheets
|
- Mounting:
- Track Mount
- Relay Contacts:
- DPDT
- Contact Ratings:
- 30 Amp