Skip to main content

Prolon PL-C1050-FCU : Fan Coil Unit Controller, 4 Digital Outputs, 1 Analog Outputs, 3 Analog Inputs, 1 Digital Input, Modbus RTU (RS485)

Prolon

$649.18
(No reviews yet) Write a Review
SKU:
PL-C1050-FCU
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added

Prolon PL-C1050-FCU : Fan Coil Unit Controller, 4 Digital Outputs, 1 Analog Outputs, 3 Analog Inputs, 1 Digital Input, Modbus RTU (RS485)

The C1050 FCU Fan Coil Unit controller is designed to control a variety of 2-pipe and 4-pipe hydronic heating and cooling units. The on-board microcontroller offers precise digital control to maximize performance. The available control sequences are fully configu- rable, either locally or remotely, using free software. The C1050 FCU uses PI (Proportional-Integral) control loops to optimize HVAC management and offers a variety of functions such as 2-pipe automatic mode change based on water temperature, automatic purge cycles to verify water temperature and prevent stagnation in coils, secondary backup heat source control, and more. The C1050 FCU will share zone demand data when connected to a Prolon network.

Features

  • Designed for hydronic systems controlling a space tempe- rature using a single space temperature sensor
  • Remote monitoring and configuration with FREE Prolon Focus software
  • Stand-alone or networked (up to 127 nodes)
  • Proportional integral (PI) control loops maximize performance
  • 4 digital outputs capable of sync or source operation and 1 analog output equipped with self-resetting fuses
  • Automatic changeover between heating and cooling on 2-pipe systems
  • Modulating valve control for heating
  • On/Off control for heating and/or cooling
  • Separate On/Off or modulating (PWM) aux heat output available
  • Configurable unoccupied mode sequences
  • Multi speed fan control options
  • Several configurable safety and efficiency limits available

Specifications

Supply 24 VAC ±10%, 50/60 Hz, Class 2
Power 2 VA (consumption), 32 VA (input)
Inputs Outdoor Air Temp / Supply Air Temp / Supply Water Temp / dry contact for proof of fan or leak alarm
Digital Outputs 4 triac outputs, 10-30 VAC source or sink, 300 mA max (self-resetting fuse)
Analog Outputs 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (self-resetting fuse)
Indication lights (LED) State of each output / Communication / Power / State of microprocessor
Microprocessor PIC18F6722, 8 bits, 40 MHz, 128KB FLASH memory
Casing Molded ABS, UL94-HB
Communication Modbus RTU (RS485) up to 127 nodes
Baud Rates 9600, 19200, 38400, 57600, 76800, 115200
Connection Removable screw-type terminal blocks (max 16 AWG)
Dimensions 6.2” x 5.2” x 2.5” (157 mm x 132 mm x 64 mm)
Weight 0.85 lbs (0.39 kg)
Environment -4 to 122 oF (-20 to 50 oC) Non-Condensing
Certification UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

 