null Skip to main content

Prolon PL-M2000-RTU : Rooftop Controller, Economizer, DCV and Dehumidification, 3 Heating Stages, FlexiZone Master, 9 Configurable Analog Inputs, 5 Triac Outputs, 3 Analog Outputs, Modbus RTU (RS485)

Prolon

Your Price:  $1,341.71
(No reviews yet) Write a Review
SKU:
PL-M2000-RTU
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
Controller TypeRooftop Controller
Inputs9 configurable analog inputs
Digital Outputs5 triac, 10-30 VAC source
Analog Outputs3 x 0-10 VDC, 40 mA max
ProtocolModbus RTU (RS485)
Supply24 VAC, Class 2
The Prolon PL-M2000-RTU is a Modbus RTU rooftop unit controller with economizer, demand controlled ventilation, dehumidification, and static pressure control, staging 3 heating stages and 2 cooling stages, expandable to 8 cooling stages with a FLX controller.

Specifications sourced from Prolon datasheet PL-DATA-M2000RTU-C/F-EN, REV 7.3.1. Verified September 18, 2026.

Overview

The M2000 RTU controls rooftop units and air treatment equipment, and acts as a master controller on a Prolon network. Sequences include economizer, preheating, CO2 levels, dehumidification, and static pressure control. It stages up to 3 stages of heating and 2 stages of cooling, expanding to 8 cooling stages once coupled with a FLX controller. The FlexiZone system manages multiple zones by evaluating the average weighted demand of customized zone groups. Its 9 analog inputs accept thermistor, dry contact, 4-20mA, 0-5 VDC, and RH% signals, individually configurable per input.

Best For

  • Rooftop units and packaged air treatment equipment
  • Zoned rooftop systems where the RTU is the FlexiZone master
  • Units requiring economizer, DCV, and dehumidification sequences
  • Large cooling plants expanding past 2 stages by pairing with an M2000 FLX

Warranty and Sourcing

ZOT Supply is an authorized Prolon distributor. Every PL-M2000-RTU ships new in factory packaging and is covered by the Prolon manufacturer warranty. For current warranty terms and RMA handling, contact ZOT Supply at 855-825-2811 or sales@zotsupply.com.

Key Features

Economizer and DCV

Economizer, demand controlled ventilation (DCV), and dehumidification sequences are available.

3 heating stages

Controls up to 3 stages of heating.

Cooling expandable to 8 stages

Controls 2 stages of cooling, and up to 8 stages once coupled with a FLX controller.

FlexiZone master

Manages multiple zones by evaluating the average weighted demand of customized zone groups.

Network master

Acts as a master controller when connected to a Prolon network.

RH% capable inputs

Input signals include thermistor, dry contact, 4-20mA, 0-5 VDC, and RH%, individually configurable per input.

  • Static pressure control and CO2 level inputs
  • Internal clock with configurable schedules and calendars
  • Configurable unoccupied mode sequences
  • A manual/off/auto switch for each of the eight outputs
  • 5 digital outputs and 3 analog outputs equipped with resettable fuses
  • Built-in protection sequences with configurable temperature limits and minimum delays

Technical Specifications

SpecificationPL-M2000-RTU
Supply24 VAC +/-10%, 50/60 Hz, Class 2
Power5 VA (consumption), 40 VA (input)
Inputs9 configurable analog inputs (outside temp / return / supply / mixed air / room, dry contact for clogged filter / schedule override / proof of fan / room setpoint / CO2 levels / static pressure / auxiliary temp). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC / RH%) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
MicroprocessorPIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
Dimensions5.39 in x 4.41 in x 2.25 in (137 mm x 112 mm x 57 mm)
Weight1.05 lbs (0.48 kg)
Environment-4 to 122 °F (-20 to 50 °C) Non-Condensing
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Documentation

Frequently Asked Questions

How many heating and cooling stages does the PL-M2000-RTU control?

Up to 3 stages of heating and 2 stages of cooling. Cooling expands to 8 stages once the RTU is coupled with an M2000 FLX controller.

Does the PL-M2000-RTU support demand controlled ventilation?

Yes. Demand controlled ventilation (DCV) and dehumidification sequences are available, along with economizer, preheating, CO2 levels, and static pressure control.

Can the PL-M2000-RTU act as a network master?

Yes. It acts as a master controller when connected to a Prolon network, and its FlexiZone system manages multiple zones by evaluating the average weighted demand of the zones using customized groups.

Can the PL-M2000-RTU read a humidity sensor?

Yes. Input signals include RH%, along with thermistor, dry contact, 4-20mA, and 0-5 VDC, individually configurable for each of the 9 inputs.

What outputs does the PL-M2000-RTU provide?

5 triac digital outputs rated 10-30 VAC source, 300 mA max with a resettable fuse, plus 3 analog outputs at 0-10 VDC, 40 mA max. Each of the eight outputs has a manual/off/auto switch.

Controller Type:
Rooftop
Digital Outputs:
5
Analog Outputs:
3
Inputs:
9
Communication:
Modbus RTU (RS485)
Product Series:
M2000

Videos Hide Videos Show Videos