Specifications from the Prolon Zone Controller (PL-VC2000) datasheet REV 7.3.0 (PL-DATA-VC2000-C/F-EN) and the VAV Zone Controller VC2000 Series Hardware Guide REV 7.3.2 (PL-HRDW-VC2000-EN), reviewed September 19, 2026.
The Prolon VC2000 series zone controllers are designed for variable air volume zoning systems. The built-in microprocessor offers precise digital control to maximize performance. The outputs and control sequences are all fully configurable, either locally or remotely, using free software or from the digital room sensor. The on-board brushless actuator provides electronic feedback on damper position. When in a network, the VC2000s can share information such as the occupancy state, the demand, the supply temperature and more.
Best For
- Single-zone VAV box control where damper position is driven by space demand
- VAV boxes or zone dampers with a 6-20 mm (0.25-0.75 in) damper shaft and at least 37 mm (1.5 in) of usable spindle
- Zones that add reheat: the triac output drives a duct heater or radiant floor sequence
- Modbus RTU or BACnet MS/TP integration into an existing building network
- FlexiZone groups where several zones are averaged into one weighted demand
Warranty
Key Features
PI Control Loops
Proportional integral (PI) control loops maximize performance
Halomo Actuator Control
Precise control of the Belimo actuator using Halomo® technology
Fused Digital + Analog Outputs
1 digital output and 1 analog output, both protected with resettable fuses
Modbus RTU or BACnet MS/TP
Supports Modbus and BACnet protocols
Standalone or Networked
Standalone or networked (up to 127 nodes)
FlexiZone Zone Grouping
FlexiZone system facilitates multiple zone management by evaluating the average weighted demand of the zones using customized groups
Additional capabilities
- Remote monitoring and configuration with free Prolon Focus software
- Configurable sequences for radiant floor and duct heater
- Analog input can monitor discharge air, occupancy, CO2 levels and more
- Works with or without a flow sensor
- Monitoring and configuration from a digital sensor
- Quick and easy installation using detachable numbered terminal blocks
- Possibility of multiple actuator control
Technical Specifications
| Supply | 24 VAC ±10%, 50/60 Hz, Class 2 |
| Power | 3 VA typical consumption, 5 VA maximum consumption, 24 VA input |
| Analog Input | 1 general purpose analog input supporting 3 types of input signals (0-5 V, 4-20 mA and thermistor) |
| Digital Sensor Port | RS485 communication port for a digital zone temperature sensor |
| Digital Output | 1 triac 10-30 VAC dry contact, 300 mA max (resettable fuse), ON/OFF or pulsed, heating or cooling |
| Analog Output | Configurable signal: 0-10 VDC, 2-10 VDC or 0-5 VDC; 40 mA max (resettable fuse), modulating, ON/OFF or pulsed, heating or cooling |
| Flow Sensor | 0-2 inch WC (0-500 Pa), not included on this model |
| Actuator | Belimo® with Halomo® technology, 45 in-lb |
| Minimum Spindle Length | 37 mm / 1.5 in (Belimo LM) |
| Spindle Diameter Range | 6-20 mm / 0.25-0.75 in (Belimo LM) |
| Communication | 1 RS485 network port (Modbus RTU or BACnet MS/TP, up to 127 nodes), and 1 RS485 port for digital sensor or computer interface |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Microprocessor | PIC18F6722, 8 bits, 40 MHz, 128KB FLASH memory |
| Casing | Molded ABS, UL94-HB |
| Dimensions | 5 in. x 5 in. x 3 in. (127 mm x 127 mm x 77 mm) |
| Weight | 1.15 lbs (0.5 kg) |
| Environment | -4 to 122 °F (-20 to 50 °C), non-condensing |
| Certification | cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1; CAN/CSA-C22.2 No. 2015-12, Signal Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class B; Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B)/NMB-3(B); RoHS Directive (2002/95/EC) |
| Country of Origin | Made in Canada |
Documentation
Frequently Asked Questions
Does the Prolon PL-VC2000 support BACnet?
Yes. The PL-VC2000 has one RS485 network port that runs either Modbus RTU or BACnet MS/TP, with up to 127 nodes on the network. A second RS485 port is reserved for a digital sensor or a computer interface.
Does the PL-VC2000 need an airflow sensor?
No. The PL-VC2000 works with or without a flow sensor and does not ship with one. The flow sensor input reads 0-2 inch WC (0-500 Pa). For a pressure independent zone, the PL-VC2000-PI is the model that includes the sensor.
How much torque does the integrated actuator produce?
45 in-lb. The actuator is a Belimo unit using Halomo technology and mounts to damper shafts 6-20 mm (0.25-0.75 in) in diameter with at least 37 mm (1.5 in) of usable spindle length, matching the Belimo LM mounting range.
What outputs does the PL-VC2000 provide?
One digital output and one analog output, both protected by resettable fuses. The digital output is a triac rated 10-30 VAC dry contact, 300 mA max, configurable ON/OFF or pulsed for heating or cooling. The analog output is 40 mA max with a configurable signal of 0-10 VDC, 2-10 VDC or 0-5 VDC, and runs modulating, ON/OFF or pulsed for heating or cooling.
What power supply does the PL-VC2000 need?
24 VAC ±10%, 50/60 Hz, Class 2. Typical consumption is 3 VA and maximum consumption is 5 VA.
What can the analog input monitor?
The general purpose analog input accepts 0-5 V, 4-20 mA or thermistor signals and can monitor discharge air, occupancy, CO2 levels and more. Zone temperature comes in separately over the RS485 digital sensor port.
Can the PL-VC2000 run standalone?
Yes. It runs standalone or networked up to 127 nodes. Outputs and control sequences are configured locally from a digital room sensor or remotely with the free Prolon Focus software.
- Controller Type:
- VAV Zone
- Digital Outputs:
- 1
- Analog Outputs:
- 1
- Inputs:
- 1
- Communication:
- Modbus RTU or BACnet MS/TP (RS485)