Skip to main content

Senva AQ2D-BD2AAAX : Duct Mount TotalSense RH/CO2 Sensor, BACnet/Modbus Output, Dual Channel CO2, 2% RH Accurracy, No Display, Buy American Act Compliant, 7-Year Limited Warranty

Senva

MSRP: $735.00
$290.00
(You save $445.00 )
(No reviews yet) Write a Review
SKU:
AQ2D-BD2AAAX
Condition:
New
Availability:
Ships in 2 Days
Adding to cart… The item has been added

Senva AQ2D-BD2AAAX : Duct Mount TotalSense Sensor, BACnet/Modbus Output, Dual Channel CO2, 2% RH Accurracy, No Display, Buy American Act Compliant, 7-Year Limited Warranty

The Senva AQ2D-BD2AAAX sensor offers a reliable and precise solution for monitoring CO2 and relative humidity (RH) within air ducts. This American-made product boasts dual channel CO2 measurement for enhanced accuracy, ideal for optimizing building environments.

Key features include:

  • Dual Channel CO2 Sensing: Delivers ±30ppm + 3% of reading accuracy within the typical occupied space CO2 range (400-2,000ppm).
  • High RH Accuracy: Measures RH with +/- 2% precision across a wide range (0-80%RH).
  • BACnet/Modbus compatible: Integrates seamlessly with existing building automation systems.
  • Long-lasting: Backed by a dependable 7-year limited warranty.

Additional specifications:

  • Power supply: 16-30VDC/24VAC
  • Selectable relay type (NO/NC)
  • Wide CO2 range: 0-10,000ppm (programmable)
  • Fast response time: 90 seconds to 90% reading
  • Compact enclosure: 4" x 4.4" x 2.1"
  • Compliant with CE and RoHS standards

This sensor caters to applications requiring accurate air quality monitoring in schools, offices, and other commercial buildings.

Specifications

Power Supply 16-30VDC/24VAC(1), 3.5W nominal, 4W max.
Protocol Output BACnet MS/TP or Modbus RTU
Relay Type Solid-state output, 1A @ 30VAC/DC, N.O.
Relay Polarity NO/NC (selectable)
CO2
 
Type Non-dispersive Infrared (NDIR)
Accuracy ±(30ppm + 3% of reading) (400-2,000ppm), -10-50ºC, 0-85%RH
±(50ppm+ 5% of reading) (2,000-5,000ppm), -10-50ºC, 0-85%RH
>5,000ppm consult factory
Resolution 1 ppm
Range 0-2,000 PPM (Default) (Programmable up to 10,000ppm)
Response time
90 seconds to 90% reading
Response Rate 1s
Temp and Pressure Compensation
Yes, barometric pressure readable over comms
Relative Humidity 2% models, +/-2% over 0 to 80%RH range
Enclosure ABS Plastic / 4.0"h x 4.4"w x x2.1"d (+6.8" probe)
Compliance CE, RoHS

 

Datasheets

pdf logo Senva AQ2D TotalSense RH/CO2 TotalSense Duct
pdf logo Senva AQ2D RH/CO2 Duct Installation
pdf logo Senva AQ2D Display Navigation Guide TotalSense Series
pdf logo Senva Made In USA Certificate 2023
Sensor Type:
Duct
Output Signal:
BACnet/Modbus Only
CO2 Element:
Yes
Humidity Element:
2%
VOC Element:
None
Temperature Element:
None
Display:
No Display
Supported Protocols:
BACnet/Modbus