The Senva CT1O-A3X is an outdoor CO2 (carbon dioxide) transmitter with a dual-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. This is the no-display version: the CO2 range, calibration settings and relay setpoints cannot be changed without the LCD menu. The 0-5 V or 0-10 V output is still selected with DIP switch 1. The LCD version is the CT1O-A3D.
ZOT Supply is an authorized distributor of Senva products.
Where this model fits
Choose the CT1O to measure outside-air CO2 for ventilation and economizer strategies, or for greenhouses. Mount it in a sheltered spot, such as under an eave on the north side, out of direct sun and rain. It is not a blanket weatherproof housing: Senva's manual lists the enclosure as IP20 / NEMA 1 and says the bottom of the outdoor enclosure must be vented to achieve NEMA 3R.
Compare mounting alternatives: CT1R-A3X-D (recessed wall, dual-channel); CT1W-A3X-D (surface wall, dual-channel); CT1D-A3X (duct, single-channel, a different CO2 channel type from this model). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.
Senva specifies a dual-channel element as standard on the CT1O. Senva's application note says automatic baseline correction is unsuited to outdoor and greenhouse measurement, where a reset toward 400 ppm misstates the reading, and that a dual-channel element limits drift without it.
This A-option model is CO2 only. In the CT1 series, B models add an active temperature transmitter, and C, D, E, F and K models carry a passive RTD or thermistor chosen to match the controller input.
Warranty and origin
Senva's warranty is a 7-year limited warranty on the electronics and 3 years on the NDIR CO2 module. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.
Senva's commerce declaration (updated 04/21/2026) lists the CT1O series as manufactured in Beaverton, Oregon, with domestic components above 65% of component cost, and declares conformance with BABAA, TAA and the ARRA Buy American provisions. It is the manufacturer's statement, not a project-specific ruling, so check it against your project's requirements.
Key facts
- Dual-channel NDIR: a reference channel corrects drift without depending on an unoccupied period. Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm. Dual-channel sensing is standard on every CT1O.
- CO2 range: 0-2000 ppm factory range. Changing the range requires the LCD version.
- Temperature: none. This is a CO2-only model.
- Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.
Specifications
| Manufacturer part number | CT1O-A3X |
|---|---|
| CO2 sensing element | Non-dispersive infrared (NDIR), dual-channel; field-replaceable |
| CO2 output scaling | 0-2000 ppm factory range. Changing the range requires the LCD version. |
| CO2 accuracy at the 0-2000 ppm output | ±(30 ppm + 3% of reading), 400-2000 ppm, 0 to 50°C, 0-85% RH |
| Drift with ABC disabled | 5 ppm/month (dual channel); may vary with environment |
| Automatic calibration (ABC) | Senva's datasheet lists automatic calibration as on by default, while Senva's outdoor application note advises against ABC for outdoor measurement. Confirm the shipped setting with Senva. It cannot be changed without the LCD version. |
| Pressure dependency | +1% of reading per kPa deviation from 101 kPa |
| CO2 response time | 60 s to 90% of reading; output updates every 1 s |
| Analog outputs | 3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V. |
| Temperature | None. This A-option model measures CO2 only. |
| CO2 setpoint relay | None on this no-display model. |
| Display | None. The CO2 range, offset adjustment and automatic calibration setting are LCD menu settings and cannot be changed on this model. DIP switch 1 still selects the 0-5 V or 0-10 V output. |
| Power supply | 24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply. |
| Operating environment | -20 to 50°C (-4 to 122°F), 0-95% RH non-condensing |
| Enclosure | Polycarbonate with aluminum tube. IP20 / NEMA 1 as listed in the manual; the enclosure bottom must be vented to achieve NEMA 3R. |
| Dimensions | 4.0 in H x 4.4 in W x 2.1 in D, plus 2.5 in solar shield |
| Warranty | Senva 7-year limited warranty on electronics; NDIR CO2 module 3 years |
Documents
Senva CT1O CO2 and Temperature Outdoor Sensor Datasheet (PDF)
CT1D / CT1O Installation Manual, 152-0381-0C, rev. 5/28/2024 (PDF)
Senva Technical Note: Dual-Channel CO2 for Outdoor and Greenhouse Applications (PDF)
Senva Commerce Declaration: BABAA, TAA, ARRA, updated 04/21/2026 (PDF)
Frequently asked questions
What CO2 range does the CT1O-A3X output?
It ships scaled 0-2000 ppm, and that range cannot be changed in the field. The 0-5000 and 0-10,000 ppm ranges need the LCD version (CT1O-A3D).
Does the CT1O-A3X measure temperature?
No. A-option models are CO2 only. B models add an active temperature transmitter, and C, D, E, F and K models add a passive RTD or thermistor.
Can the CT1O-A3X switch a relay at a CO2 setpoint?
No. This no-display model has no CO2 setpoint relay. If relay control is required, choose the LCD version (CT1O-A3D).
Why is the CT1O dual-channel?
Senva specifies a dual-channel element as standard on the CT1O. Its application note explains that automatic baseline correction assumes the sensor periodically returns to about 400 ppm, which does not hold for outdoor or greenhouse measurement; the dual-channel element limits drift without relying on it. Drift with ABC disabled is rated 5 ppm/month.
Related CT1 models
- CT1O-A3D: same sensor with LCD
- CT1O-B3X: Temperature Transmitter
- CT1O-C3X: 100 Ohm Platinum RTD
- CT1O-D3X: 1K Platinum RTD
- CT1O-E3X: 10K Type II Thermistor
- CT1O-F3X: 10K Type III Thermistor
Specifications are taken from Senva's CT1D / CT1O installation manual 152-0381-0C (rev. 5/28/2024) and the Senva CT1O datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.
Warranty
Senva 7-year limited warranty on electronics; 3-year warranty on the NDIR CO2 sensing module. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.
- Sensor Type:
- Outside Air
- Humidity Element:
- None
- CO2 Element:
- Yes
- Temperature Element:
- None
- Display:
- No Display
- VOC:
- No
- Mounting:
- Outdoor
- CO2 Channel:
- Dual Channel
- CO2 Range:
- 2000ppm Fixed
- Country of Origin:
- USA
- CO2 Setpoint Relay:
- None