Senva CT1O-F3X Outdoor Dual-Channel CO2/Temperature Sensor, 10K Type III Thermistor, No Display, 4-20 mA/0-5/0-10 V

Senva

MSRP: $665.49
Your Price:  $326.17
(You save $339.32 )
(No reviews yet) Write a Review
SKU:
CT1O-F3X
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
CO2 SensingNDIR, Dual Channel
CO2 Range0-2000 ppm (factory)
Temperature10K Type III
DisplayNone
Outputs4-20 mA / 0-5 V / 0-10 V
MountingOutdoor

The Senva CT1O-F3X is an outdoor CO2 (carbon dioxide) and temperature sensor with a dual-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. It also carries a passive 10K Type III Thermistor. This is the no-display version: the CO2 range, calibration settings and relay setpoints cannot be changed without the LCD menu. The 0-5 V or 0-10 V output is still selected with DIP switch 1. The LCD version is the CT1O-F3D.

Authorized Distributor

ZOT Supply is an authorized distributor of Senva products.

Where this model fits

Choose the CT1O to measure outside-air CO2 for ventilation and economizer strategies, or for greenhouses. Mount it in a sheltered spot, such as under an eave on the north side, out of direct sun and rain. It is not a blanket weatherproof housing: Senva's manual lists the enclosure as IP20 / NEMA 1 and says the bottom of the outdoor enclosure must be vented to achieve NEMA 3R.

Compare mounting alternatives: CT1R-F3X-D (recessed wall, dual-channel); CT1D-F3X (duct, single-channel, a different CO2 channel type from this model). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.

Senva specifies a dual-channel element as standard on the CT1O. Senva's application note says automatic baseline correction is unsuited to outdoor and greenhouse measurement, where a reset toward 400 ppm misstates the reading, and that a dual-channel element limits drift without it.

The 10K Type III Thermistor is a passive element. The controller reads its resistance directly, so the input must be set for the matching 10K Type III curve. If the controller needs a 4-20 mA or voltage temperature signal, pick the B (transmitter) option instead.

Warranty and origin

Senva's warranty is a 7-year limited warranty on the electronics and 3 years on the NDIR CO2 module. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.

Senva's commerce declaration (updated 04/21/2026) lists the CT1O series as manufactured in Beaverton, Oregon, with domestic components above 65% of component cost, and declares conformance with BABAA, TAA and the ARRA Buy American provisions. It is the manufacturer's statement, not a project-specific ruling, so check it against your project's requirements.

Key facts

  • Dual-channel NDIR: a reference channel corrects drift without depending on an unoccupied period. Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm. Dual-channel sensing is standard on every CT1O.
  • CO2 range: 0-2000 ppm factory range. Changing the range requires the LCD version.
  • Temperature: passive 10K Type III Thermistor, 10 kΩ at 25°C (10K Type III curve).
  • Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.

Specifications

Manufacturer part numberCT1O-F3X
CO2 sensing elementNon-dispersive infrared (NDIR), dual-channel; field-replaceable
CO2 output scaling0-2000 ppm factory range. Changing the range requires the LCD version.
CO2 accuracy at the 0-2000 ppm output±(30 ppm + 3% of reading), 400-2000 ppm, 0 to 50°C, 0-85% RH
Drift with ABC disabled5 ppm/month (dual channel); may vary with environment
Automatic calibration (ABC)Senva's datasheet lists automatic calibration as on by default, while Senva's outdoor application note advises against ABC for outdoor measurement. Confirm the shipped setting with Senva. It cannot be changed without the LCD version.
Pressure dependency+1% of reading per kPa deviation from 101 kPa
CO2 response time60 s to 90% of reading; output updates every 1 s
Analog outputs3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V.
TemperaturePassive 10K Type III Thermistor, 10 kΩ at 25°C (10K Type III curve). It is wired on its own terminals as a resistance signal; it is not an analog transmitter output.
CO2 setpoint relayNone on this no-display model.
DisplayNone. The CO2 range, offset adjustment and automatic calibration setting are LCD menu settings and cannot be changed on this model. DIP switch 1 still selects the 0-5 V or 0-10 V output.
Power supply24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply.
Operating environment-20 to 50°C (-4 to 122°F), 0-95% RH non-condensing
EnclosurePolycarbonate with aluminum tube. IP20 / NEMA 1 as listed in the manual; the enclosure bottom must be vented to achieve NEMA 3R.
Dimensions4.0 in H x 4.4 in W x 2.1 in D, plus 2.5 in solar shield
WarrantySenva 7-year limited warranty on electronics; NDIR CO2 module 3 years

Documents

Frequently asked questions

What CO2 range does the CT1O-F3X output?

It ships scaled 0-2000 ppm, and that range cannot be changed in the field. The 0-5000 and 0-10,000 ppm ranges need the LCD version (CT1O-F3D).

How does the CT1O-F3X report temperature?

Through a passive 10K Type III Thermistor on its own terminals. The controller reads the resistance directly and must be set for the 10K Type III curve; Senva's resistance-temperature tables are linked under Documents.

Can the CT1O-F3X switch a relay at a CO2 setpoint?

No. This no-display model has no CO2 setpoint relay. If relay control is required, choose the LCD version (CT1O-F3D).

Why is the CT1O dual-channel?

Senva specifies a dual-channel element as standard on the CT1O. Its application note explains that automatic baseline correction assumes the sensor periodically returns to about 400 ppm, which does not hold for outdoor or greenhouse measurement; the dual-channel element limits drift without relying on it. Drift with ABC disabled is rated 5 ppm/month.

Related CT1 models

Specifications are taken from Senva's CT1D / CT1O installation manual 152-0381-0C (rev. 5/28/2024) and the Senva CT1O datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.

Warranty

Senva 7-year limited warranty on electronics; 3-year warranty on the NDIR CO2 sensing module. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.

Sensor Type:
Outside Air
Humidity Element:
None
CO2 Element:
Yes
Temperature Element:
10K Type III
Display:
No Display
VOC:
No
Mounting:
Outdoor
CO2 Channel:
Dual Channel
CO2 Range:
2000ppm Fixed
Country of Origin:
USA
CO2 Setpoint Relay:
None