null Skip to main content

Senva CT1R-E3D Recessed CO2/Temperature Sensor, 10K Type II Thermistor, LCD & Setpoint Relay, 4-20 mA/0-5/0-10 V

Senva

MSRP: $505.75
Your Price:  $248.15
(You save $257.60 )
(No reviews yet) Write a Review
SKU:
CT1R-E3D
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
CO2 SensingNDIR, Single Channel
CO2 Range2000 / 5000 / 10,000 ppm
Temperature10K Type II
DisplayLCD + Setpoint Relay
Outputs4-20 mA / 0-5 V / 0-10 V
MountingRecessed Wall

The Senva CT1R-E3D is a recessed room CO2 (carbon dioxide) and temperature sensor with a single-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. It also carries a passive 10K Type II Thermistor. The LCD and push-button menu set range, calibration and the built-in setpoint relay.

Authorized Distributor

ZOT Supply is an authorized distributor of Senva products.

Where this model fits

Choose the CT1R when the sensor should sit nearly flush with the wall. It mounts in a standard junction box or straight into drywall using its built-in clamps. Mount it vertically at light-switch height on an interior wall, away from supply air, doors, windows and heat sources.

Compare mounting alternatives: CT1W-E3D (surface wall, single-channel); CT1D-E3D (duct, single-channel); CT1O-E3D (outdoor, dual-channel as standard, a different CO2 channel type from this model). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.

Single-channel models rely on automatic baseline correction (ABC), which tracks the lowest CO2 level the space reaches. That suits offices, classrooms and other spaces that empty out regularly. For spaces occupied around the clock, Senva recommends a dual-channel model such as the CT1R-E3D-D.

The 10K Type II Thermistor is a passive element. The controller reads its resistance directly, so the input must be set for the matching 10K Type II curve. If the controller needs a 4-20 mA or voltage temperature signal, pick the B (transmitter) option instead.

Warranty and origin

Senva covers the CT1 series with a 7-year limited warranty. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.

Senva's commerce declaration (updated 04/21/2026) lists the CT1R series as manufactured in Beaverton, Oregon, with domestic components above 65% of component cost, and declares conformance with BABAA, TAA and the ARRA Buy American provisions. It is the manufacturer's statement, not a project-specific ruling, so check it against your project's requirements.

Key facts

  • Single-channel NDIR with automatic baseline correction (ABC). Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm.
  • CO2 range: 0-2000 ppm default; 0-5000 ppm or 0-10,000 ppm selectable in the LCD menu (SCL).
  • Temperature: passive 10K Type II Thermistor, 10 kΩ at 25°C (10K Type II curve).
  • CO2 setpoint relay: solid-state, normally open, 1 A at 30 VAC/DC, adjustable from the LCD menu.
  • Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.

Specifications

Manufacturer part numberCT1R-E3D
CO2 sensing elementNon-dispersive infrared (NDIR), single-channel
CO2 output scaling0-2000 ppm default; 0-5000 ppm or 0-10,000 ppm selectable in the LCD menu (SCL).
CO2 accuracy±(30 ppm + 3% of reading), 400-2000 ppm, -10 to 50°C
±(50 ppm + 5% of reading), 2000-5000 ppm, -10 to 50°C
±(100 ppm + 10% of reading), 5000-10,000 ppm, 0 to 50°C
Drift with ABC disabled35 ppm/month; may vary with environment
Automatic calibration (ABC)On by default; can be switched on or off in the LCD menu (CAL).
CO2 response time60 s to 90% of reading; output updates every 1 s
Analog outputs3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V.
TemperaturePassive 10K Type II Thermistor, 10 kΩ at 25°C (10K Type II curve). It is wired on its own terminals as a resistance signal; it is not an analog transmitter output.
CO2 setpoint relaySolid-state, normally open, 1 A at 30 VAC/DC. On point (SPH) 500 ppm to full scale, 800 ppm default; off point (SPL) 400 ppm to full scale, 700 ppm default.
DisplayLCD with push-button menu: scaling (SCL), relay setpoints (SPH, SPL), offset adjustment (ADJ, ±250 ppm) and automatic calibration (CAL).
Power supply24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply.
Operating environment-10 to 50°C (14 to 122°F), 0-95% RH non-condensing
EnclosureABS plastic, IP20 / NEMA 1
Dimensions5.66 in H x 3.00 in W x 0.36 in D from the wall (1.69 in D including the recessed portion)
WarrantySenva 7-year limited warranty

Documents

Frequently asked questions

What CO2 range does the CT1R-E3D output?

It ships scaled 0-2000 ppm. The LCD menu can change the scale to 0-5000 ppm or 0-10,000 ppm.

How does the CT1R-E3D report temperature?

Through a passive 10K Type II Thermistor on its own terminals. The controller reads the resistance directly and must be set for the 10K Type II curve; Senva's resistance-temperature tables are linked under Documents.

Does the CT1R-E3D have a CO2 setpoint relay?

Yes. It has a solid-state, normally open relay rated 1 A at 30 VAC/DC. The on and off points are set in the LCD menu and default to 800 ppm and 700 ppm.

Does the CT1R-E3D need field calibration?

Senva calibrates it at the factory and does not recommend routine field calibration. Automatic baseline correction (ABC) tracks low ambient CO2 to correct long-term drift; the LCD menu also has a ±250 ppm offset adjustment.

Related CT1 models

Specifications are taken from Senva's CT1R installation manual 152-0132-0G (rev. 05/24/2024) and the Senva CT1R / CT1W datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.

Warranty

Senva 7-year limited warranty. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.

Sensor Type:
Wall Mount
Temperature Element:
10K Type II
Supported Protocols:
None
Humidity Element:
None
CO2 Element:
Yes
Setpoint:
Setpoint
Display:
LCD Display
Material:
Plastic
Mounting:
Recessed
CO2 Channel:
Single Channel
CO2 Range:
2000/5000/10000ppm Selectable
CO2 Setpoint Relay:
Solid-State Relay
Country of Origin:
USA