The Senva CT1W-E3X is a surface-mount room CO2 (carbon dioxide) and temperature sensor with a single-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. It also carries a passive 10K Type II Thermistor. This is the no-display version: the CO2 range and calibration settings cannot be changed without the LCD menu, and it has no setpoint relay. The 0-5 V or 0-10 V output is still selected with DIP switch 1. The LCD version is the CT1W-E3D.
ZOT Supply is an authorized distributor of Senva products.
Where this model fits
Choose the CT1W for surface mounting on a wall. The lid locks at all four snaps, which suits schools and public areas. Mount it vertically at light-switch height on an interior wall, away from supply air, doors, windows and heat sources.
Compare mounting alternatives: CT1R-E3X (recessed wall, single-channel); CT1D-E3X (duct, single-channel); CT1O-E3X (outdoor, dual-channel as standard, a different CO2 channel type from this model). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.
Single-channel models rely on automatic baseline correction (ABC), which tracks the lowest CO2 level the space reaches. That suits offices, classrooms and other spaces that empty out regularly. For spaces occupied around the clock, Senva recommends a dual-channel model.
The 10K Type II Thermistor is a passive element. The controller reads its resistance directly, so the input must be set for the matching 10K Type II curve. If the controller needs a 4-20 mA or voltage temperature signal, pick the B (transmitter) option instead.
Warranty and origin
Senva covers the CT1 series with a 7-year limited warranty. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.
Senva describes its CT1 room sensors as made in the USA. The CT1W series is not named on Senva's 2026 commerce declaration, so ask Senva for written confirmation if your project needs BABAA, TAA or Buy American documentation.
Key facts
- Single-channel NDIR with automatic baseline correction (ABC). Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm.
- CO2 range: 0-2000 ppm factory range. Changing the range requires the LCD version.
- Temperature: passive 10K Type II Thermistor, 10 kΩ at 25°C (10K Type II curve).
- CO2 setpoint relay: none on this no-display model.
- Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.
Specifications
| Manufacturer part number | CT1W-E3X |
|---|---|
| CO2 sensing element | Non-dispersive infrared (NDIR), single-channel |
| CO2 output scaling | 0-2000 ppm factory range. Changing the range requires the LCD version. |
| CO2 accuracy at the 0-2000 ppm output | ±(30 ppm + 3% of reading), 400-2000 ppm, -10 to 50°C |
| Drift with ABC disabled | 35 ppm/month; may vary with environment |
| Automatic calibration (ABC) | On at the factory; it cannot be changed without the LCD version. |
| CO2 response time | 60 s to 90% of reading; output updates every 1 s |
| Analog outputs | 3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V. |
| Temperature | Passive 10K Type II Thermistor, 10 kΩ at 25°C (10K Type II curve). It is wired on its own terminals as a resistance signal; it is not an analog transmitter output. |
| CO2 setpoint relay | None. Senva fits the setpoint relay only on display models. |
| Display | None. The CO2 range, offset adjustment and automatic calibration setting are LCD menu settings and cannot be changed on this model. DIP switch 1 still selects the 0-5 V or 0-10 V output. |
| Power supply | 24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply. |
| Operating environment | -10 to 50°C (14 to 122°F), 0-95% RH non-condensing |
| Enclosure | ABS plastic, IP20 / NEMA 1 |
| Dimensions | 5.66 in H x 3.0 in W x 1.07 in D (surface mount, per Senva datasheet) |
| Warranty | Senva 7-year limited warranty |
Documents
Senva CT1R / CT1W CO2 and Temperature Datasheet (PDF)
CT1W Installation Manual, 152-0410-0D, rev. 5/24/2024 (PDF)
Senva Thermistor and RTD Resistance-Temperature Tables (PDF)- Surface Enclosure CAD Drawing (DWG)
Frequently asked questions
What CO2 range does the CT1W-E3X output?
It ships scaled 0-2000 ppm, and that range cannot be changed in the field. The 0-5000 and 0-10,000 ppm ranges need the LCD version (CT1W-E3D).
How does the CT1W-E3X report temperature?
Through a passive 10K Type II Thermistor on its own terminals. The controller reads the resistance directly and must be set for the 10K Type II curve; Senva's resistance-temperature tables are linked under Documents.
Does the CT1W-E3X have a CO2 setpoint relay?
No. Senva fits the setpoint relay only on display models, such as the CT1W-E3D.
Does the CT1W-E3X need field calibration?
Senva calibrates it at the factory and does not recommend routine field calibration. Automatic baseline correction (ABC) tracks low ambient CO2 to correct long-term drift.
Related CT1 models
- CT1W-E3D: same sensor with LCD and setpoint relay
- CT1W-A3X: CO2 only, no temperature element
- CT1W-B3X: Temperature Transmitter
Specifications are taken from Senva's CT1W installation manual 152-0410-0D (rev. 5/24/2024) and the Senva CT1R / CT1W datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.
Warranty
Senva 7-year limited warranty. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.
- Sensor Type:
- Wall Mount
- Temperature Element:
- 10K Type II
- Supported Protocols:
- None
- Humidity Element:
- None
- CO2 Element:
- Yes
- Setpoint:
- No Setpoint
- Override:
- No Override
- Display:
- No Display
- Material:
- Plastic
- Mounting:
- Surface
- CO2 Channel:
- Single Channel
- CO2 Range:
- 2000ppm Fixed
- CO2 Setpoint Relay:
- None