Senva TG Series sensors can be ordered as individual sensors or as any dual combination of CO/NO2/Propane/Methane/H2S sensor in a shared enclosure. Detect Methane/Propane leaks and monitor for elevated CO levels, all in one unit.
The analog output model features 2 outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost effective coverage of large areas. The unit can also act as a stand alone controller, utilizing the relay for exhaust fan operation or the output for direct control of a VFD.

APPLICATIONS

  • Ensure adequate air flow in occupied spaces
  • Ideal fo parking lot garages 
  • Monitor multiple toxic gases with one mounted unit
  • Alert occupants of elevated gas levels
  • Directly control exhaust fans

Specifications

Power Supply 15-30 VDC/24VAC(1), 4 W max, 160 mA max.
Analog Outputs 0-10 V (default), 0-5V, 1-5 V and 4-20 mA (menu selectable)
Display 3-1/2 digit LCD
Audible Alarm Exposure 85dB Piezo transducer
H2S Sensor
Performance
  • Type : Electrocmechancial
  • Detection Tange: 0-100 ppm
  • Accuracy: ±5% of range
  • Resolution:1 ppm
  • Life expectancy: 5 Years
  • Coverage Area: 5000-7500 square feet 
Carbon Dioxide (CO2)
  • Type: Non-Dispersive Infrared (NDIR)
  • Accuracy(4):±(30ppm +3% of reading) (400-2000ppm), @-10-50°C ±(50ppm +5% of reading) Standard (2000-5000ppm), ±(50ppm+3% of reading) Dual Channel (2000-5000ppm), ±(100ppm+10% of reading) (5000-10000ppm)
  • Resolution: 1 ppm
  • Life expectancy: 15 years
  • Coverage Area: 5000-7500 square feet
Enclosure (Wall & Duct) Material ABS/Polycarbonate
 
Enclosure Style:
Wall
Gas Element:
Carboon Dioxide (CO2) / Hydrogen Sulfide(H2S)
Display:
LCD Display
Sensor Output:
0-5V, 0-10V, 4-20mA

Videos Hide Videos Show Videos