null Skip to main content

ACI A/DLP-004-W-U-D-B-1-C-0P-S : Differential Low Pressure Transmitter, 0-4 in WC Unidirectional, 0-10 VDC Output, +/-0.25% Accuracy, LCD, Pitot Tube Included, No NIST Certificate, 5-Yr Warranty, Made in USA

ACI

MSRP: $501.00
$208.42
(You save $292.58 )
(No reviews yet) Write a Review
SKU:
A/DLP-004-W-U-D-B-1-C-0P-S
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
TypeDifferential / Air
Range0-4 in WC
DirectionUnidirectional
Output0-10 VDC
Accuracy+/-0.25% FSO
DisplayLCD
MountingDIN Rail or Panel
NIST CertNone

The ACI A/DLP-004-W-U-D-B-1-C-0P-S is part of ACI's DLP Series Differential Low Pressure Transmitter family - a factory-calibrated, custom-ranged variant configured for a 0 to 4 inch WC unidirectional range with a 0-10 VDC output (3-wire VAC or VDC powered) and +/-0.25% FSO accuracy. The DLP uses a piezoresistive silicon sensing element with a hinged enclosure cover and integrated locking tab for easy access to the zero function. This SKU has an integrated 5-digit LCD display for live pressure indication on the unit cover. A 7" aluminum duct-static pitot tube (A/PT-DLP) ships with this SKU - it threads into the back of the enclosure for direct duct-static measurement without separate pickup ports. This unit is factory-calibrated with NIST-traceable equipment but ships without a printed certificate. If your project requires documented calibration, see the matching variants with 3P or 5P NIST suffix. Made in USA by ACI in Middleton, Wisconsin.

Best For

This range is best suited for standard HVAC duct and air-handler pressure measurements: duct static pressure, VAV box differential, filter loading on commercial AHUs, fan inlet/outlet pressure drop, RTU economizer logic, and air-flow measurement via pitot tube. Per ACI's published applications: building and duct static pressure, filter monitoring, air flow measurement, and process control. This is a factory-calibrated custom-range SKU - the DIP switches are set at the factory and cannot be field-adjusted (see I0000977 installation manual). If your application needs to switch between ranges in the field, see the legacy multi-range catalog SKUs (A/DLP-001, A/DLP-010, A/DLP-040 in their standard configurations).

5-YEAR WARRANTY
MADE IN USA
Backed by ACI's 5-Year Limited Warranty. Manufactured in Middleton, Wisconsin, USA, with factory NIST-traceable calibration on every unit. ZOT Supply is an authorized ACI distributor.

Key Features

Factory-Calibrated for Your Exact Range

This DLP is factory-calibrated to the 0 to 4 inch WC range using NIST-traceable equipment - DIP switches are set at the factory and the span calibration is locked. The unit ships ready to install with full-scale output across your specified range, giving you the best resolution and accuracy at the working pressure of your application.

Piezoresistive Silicon Element

A piezoresistive silicon sensing element senses differential pressure and provides a linear analog output proportional to the specified range. Silicon technology provides excellent long-term stability and minimal warmup shift versus older diaphragm-based designs.

0-10 VDC Output Signal

0-10 VDC output, 3-wire VAC or VDC powered (15-36 VDC into >5K ohm load, or 24 VAC +/-10%). Output limited to 10.5 VDC maximum. The full 0-10 V swing gives better resolution at the controller A/D for span-critical applications.

+/-0.25% FSO Accuracy

Accuracy specification includes linearity, hysteresis, and repeatability at 71 deg F (21.5 deg C) typical. Thermal effects: +/-0.067% FSO per deg F (0.12% FSO per deg C) relative to 71 deg F. This is the enhanced +/-0.25% accuracy class - useful for applications where you need tighter control limits or audit-grade documentation.

5-Digit LCD Display

An integrated 5-digit LCD on the unit cover provides direct live readings of differential pressure - useful for installation, commissioning, and field troubleshooting. The LCD also shows an AUTOZERO icon during zero-mode entry and an OUT OF RANGE icon when the differential exceeds the calibrated range. Engineering units (inWC or Pa) can be switched via DIP SW3 position 3.

Pushbutton Zero Function

An on-board pushbutton ZERO performs in-place offset calibration. Procedure: ensure no pressure at HI or LO fittings (or connect a loop between them), then press and hold ZERO for more than 3 seconds. Long-term drift is primarily an offset shift (not a span shift) - periodic re-zeroing eliminates drift without service interruption.

Includes 7" Aluminum Duct-Static Pitot Tube

This SKU ships with the A/PT-DLP DLP-specific aluminum duct-static pitot tube (7" total length, 6.75" insertion). The pitot threads directly into the back of the DLP enclosure with the included rubber washer for a sealed connection. When the pitot is installed, the silicone tubing on the High Pressure (H) barb is removed and re-routed to the pitot barb fitting - leaving the H barb open to atmosphere as the reference.

Finger Pushbutton Terminal Blocks

Finger-pushbutton (spring) terminal blocks accept 16-24 AWG wire - no screwdriver required for routine connections. The enclosure ships with a watertight cordgrip installed; for 1/2" NPT conduit, remove the cordgrip and install your conduit fitting. ACI recommends shielded cable with the shield grounded only at the controller end.

Robust Overpressure Protection

Proof pressure of 350 inch WC (87.12 kPa) and burst pressure of 550 inch WC (136.9 kPa) - well above this SKU's operating range. Tolerates transient overpressure from duct damper slams, fan start-up surges, and commissioning test pressures without sensor damage. Media must be non-corrosive, non-ionic gases (dry air or inert gases).

Technical Specifications

SpecificationDetail
Sensor StyleActive differential low pressure transmitter, factory-calibrated single range
Sensing ElementPiezoresistive silicon
Measured ValueDifferential pressure (HI - LO ports)
Pressure Range (Factory Set)0 to 4 inch WC (Unidirectional) - DIP switches locked at factory
Output Signal0-10 VDC - 3-wire VAC or VDC powered
Accuracy+/-0.25% FSO (includes linearity, hysteresis, repeatability at 71 deg F)
Thermal Effects+/-0.067% FSO per deg F (0.12% FSO per deg C) relative to 71 deg F
Response Time (0-100% FSO)4 seconds
Output Update Rate0.5 second intervals
Zero FunctionPushbutton ZERO (hold >3 sec)
DisplayYes - 5-Digit LCD on cover
Proof Pressure350 inch WC (87.12 kPa)
Burst Pressure550 inch WC (136.9 kPa)
Power Supply15-36 VDC into >5K ohm load, or 24 VAC +/-10% 50/60 Hz
Supply Current6 mA maximum (0.18 VA)
Operating Temperature-4 to 185 deg F (-20 to 85 deg C)
Compensated Temperature Range32 to 122 deg F (0 to 50 deg C)
Storage Temperature-22 to 185 deg F (-30 to 85 deg C)
Operating Humidity10-95% RH non-condensing
Media CompatibilityNon-corrosive, non-ionic gases (dry air, inert gases)
Pressure FittingNickel-plated brass or stainless steel push-on, accepts 1/4" OD x 0.170" ID poly tubing
EnclosureFlame-retardant polycarbonate, UL94-5VA
ConduitWatertight cordgrip installed; accepts 1/2" NPT conduit when cordgrip removed
WiringFinger pushbutton (spring) terminal blocks, accepts 16-24 AWG
Dimensions5.56 x 4.35 x 2.25 in (141.29 x 110.43 x 57.24 mm); 6.21 in deep with cordgrip
Weight0.85 lb (0.385 kg)
Optional AccessoriesPitot Tube Included
NIST CalibrationNo NIST Certificate - Factory NIST-traceable calibration
ApprovalsCE, RoHS2, WEEE, REACH
ManufacturerACI (Automation Components, Inc.) - Middleton, WI USA
Manufacturer Part NumberA/DLP-004-W-U-D-B-1-C-0P-S
Warranty5-Year ACI Limited Warranty

What's In the Box

Included
  • DLP transmitter, factory-calibrated to the specified range
  • Watertight cordgrip pre-installed (accepts 1/2" NPT conduit when removed)
  • Two (2) #8 x 3/4" self-drilling panel-mount screws
  • Installation & Operation Instructions (ACI document I0000977)
  • 5-digit LCD display (integrated on enclosure cover)
  • A/PT-DLP 7" aluminum duct-static pitot tube with rubber sealing washer
Accessories (Sold Separately)

Documentation

Frequently Asked Questions

What does the A/DLP-004-W-U-D-B-1-C-0P-S measure and output?

It measures differential air pressure in the 0 to 4 inch WC range (unidirectional) and outputs a linear 0-10 VDC analog signal proportional to the pressure. Accuracy is +/-0.25% FSO including linearity, hysteresis, and repeatability. The DLP is intended for HVAC and process applications using dry air or other non-corrosive, non-ionic gases - not liquids, refrigerants, or corrosive vapors.

Can I change the range or output mode in the field?

No - this is a custom-calibrated DLP. The range and output mode are set at the factory and the DIP switches are locked (per ACI's I0000977 installation manual: "This is a custom calibrated DLP and the output span switches CANNOT be adjusted"). If you need a field-selectable multi-range DLP, see the legacy catalog SKUs (A/DLP-001-W-U-N-A-0, A/DLP-010-W-U-N-A-0, A/DLP-040-W-U-N-A-0 and their LCD variants) - those ship with 8 selectable ranges per unit.

Should I use unidirectional or bidirectional mode?

This SKU is unidirectional (0 to +X) - correct for almost all HVAC applications where the HI port is always at higher pressure than the LO port: duct static measurements, filter loading, room-to-corridor pressurization. For applications where pressure can swing across zero (reversible-flow systems, makeup-air with mode switching, isolation rooms that flip between positive and negative pressure), order a bidirectional variant (direction code B) where 0 differential maps to mid-scale output.

When and how should I zero the device?

Zero on initial installation, after re-positioning, and any time the unit reads a non-zero offset with no pressure applied. Procedure: (1) Remove the tubing from the HI and/or LO pressure fittings (or short them together to neutralize external pressure). (2) Press and hold the ZERO button for more than 3 seconds, then release. For LCD variants, the AUTOZERO icon will appear on the screen during zero mode and flash twice on successful completion. The Span calibration is digital and factory-set; units requiring Span re-calibration must be returned to ACI.

Does this come with a NIST certificate?

No - this is the standard 0P (no NIST certificate) variant. The DLP is factory-calibrated using NIST-traceable equipment, but no printed certificate is shipped. If your project requires a documented certificate of calibration, see the 3P (3-point at 10%/50%/90% FSO) or 5P (5-point at 10%/30%/50%/70%/90% FSO) variants of the same configuration.

What accessories do I need for installation?

Required: pressure-sense tubing (0.25" OD x 0.17" ID medical-grade PVC - A/10' TUBE, A/20' TUBE, A/50' TUBE, A/100' TUBE), 16-24 AWG shielded cable, and a 24 VAC or 15-36 VDC power supply. Application-dependent: pitot tube for direct duct-static measurement - the DLP-specific A/PT-DLP (7") threads into the back of the enclosure, or use generic ACI pitots (PT 3", PT 5.2", PT 7.5", PT 9.7" with foam gaskets; SPT-3.5" / SPT-8.0" static; VPT / VPT-8" velocity). DIN rail clip for panel mounting: A/DRC-DLP (35 mm). Pickup ports for wall/room pressure taps: A/SP-PUP, A/R-PUP, A/R2-PUP, or outdoor weatherproof A/O-PUP-H / A/O-PUP-V. Keep tubing runs under 75 feet (23 meters).

How does the DLP compare to the MLP2?

Both are differential low-pressure transmitters using the same piezoresistive silicon sensing technology. DLP advantages: larger enclosure with hinged cover for easier zero/output access, optional 5-digit LCD display on the unit cover, watertight cordgrip for environmental sealing, factory-bundled Pitot/DIN rail accessory options, broader range coverage (up to 0-40" WC vs MLP2's 0-30" WC). MLP2 advantages: smaller compact form factor (designed for OEM/panel density), integrated DIN rail foot, lower price point. Choose DLP for applications needing the LCD, larger enclosure, or wider range options; choose MLP2 for OEM/panel-density installations.

What media can this sensor handle?

Dry air and inert non-conductive gases only: clean ambient air, nitrogen, argon, dry CO2. The DLP is NOT compatible with: liquids, refrigerants, corrosive gases (chlorine, ammonia, hydrogen sulfide, acid fumes), conductive gases, condensing moisture, or media containing particulates. Liquid contamination at the sensor diaphragm causes immediate damage and voids the warranty. For wet/wet differential pressure applications, see Senva PW30 or Belimo 22PDP series in the Liquid Pressure subcategory.

What's the warranty?

5-Year ACI Limited Warranty - covers manufacturing defects in materials and workmanship under normal use. Manufactured in Middleton, Wisconsin, USA. ZOT Supply is an authorized ACI distributor; warranty claims are processed directly with ACI. The full warranty terms are in the front of ACI's Sensors & Transmitters catalog.

Series:
DLP
Pressure Range:
0 to 4 inch WC
Range Class:
Medium
Direction:
Unidirectional
Output Signal:
0-10 VDC
Accuracy:
+/-0.25% FSO
Display:
Yes (LCD)
NIST Certificate:
None
Mounting:
DIN Rail / Panel
Made in USA:
Yes