The ACI AFS-460 is a general-purpose differential pressure switch (metal housing) for HVAC and Energy Management applications including airflow proving, filter-blockage detection, fan-status verification, alarms, and control sequences. The plated galvanized-steel housing contains a diaphragm, calibration spring, and a single snap-acting SPST-NC contact with manual reset (operator intervention required after every trip - the switch latches in its tripped state and must be manually reset). Configured for a set-point range of 0.4-12 inWC, the switch accepts sample lines via compression fitting (integral ferrule and nut accepting 1/4" OD rigid or semi-rigid metallic tubing). Can be used to sense positive, negative, or differential air pressure (use with ACI A/SPT or A/VPT sampling tubes). Made in USA by ACI in Middleton, Wisconsin.
This switch is best suited for safety-critical and operator-acknowledgment applications where the system must NOT auto-recover after a fault - common uses include high-static filter-clog alarms, fan-failure shutdowns requiring maintenance attention, freeze-protection lockouts, and any process where an operator should physically inspect the unit before the system re-arms. Per ACI's published applications: monitoring filter blockage, proof of flow, prove excessive or insufficient flow, alarms and control.
Key Features
A single-pole single-throw normally-closed (SPST-NC) snap-acting contact with manual reset button on the enclosure. After a pressure trip, the contact remains in its switched state until the operator presses the reset button - useful for safety-critical sequences where automatic recovery is undesirable (fan shutdowns, freeze-protection lockouts, filter-replacement alarms). Rated 15A at 125, 250, or 277 VAC with strong inductive rating (1/4 hp at 125 VAC, 1/2 hp at 250 VAC).
Set point is field-adjustable across the entire 0.4-12 inWC range via the on-board adjustment screw. Calibration procedure: turn the adjustment screw counterclockwise until motion stops, then turn 4 complete turns clockwise to engage the spring; the next 10 turns are the calibration range. Each full turn represents approximately 1.16 inWC per full turn (10 calibration turns total). ACI recommends using a digital manometer or other measuring device to confirm the actual set point during calibration.
Integral compression fittings with ferrule and nut accept 1/4" OD rigid or semi-rigid metallic tubing - the professional choice for permanent installations where vibration resistance and long-term seal integrity matter. For sample lines up to 10 feet, 1/4" OD tubing is sufficient; for runs up to 20 feet, use 1/4" ID tubing; for runs 20-60 feet, step up to 1/2" ID tubing to maintain response time. If flexible tubing is preferred, an optional 1/4" OD slip-on adapter (P/N 18311) is available, or order the -112 variant with barbed fittings included.
The diaphragm must be mounted in any vertical plane to achieve the lowest specified operating set point - mounting with the diaphragm horizontal will introduce gravity bias and prevent the switch from reaching its lowest rated trip point. Surface-mount via two 3/16" diameter holes in the integral mounting bracket (mounting holes are 3-7/8" apart). Avoid mounting with the sample-line connections pointing upward to prevent condensate from accumulating in the tubing.
Screw-top terminals with cup washers (8-32 screws on AFS-460) accept standard 14-22 AWG wire. The enclosure cover has a 7/8" opening that accepts 1/2" conduit. An enclosure cover guards against accidental contact with the live terminal screws and the set-point adjusting screw.
Plated galvanized steel housing provides corrosion resistance and mechanical durability for HVAC equipment-room and rooftop-unit installations. The internal diaphragm material is compatible with air. Maximum pressure tolerance: 0.5 psi (0.03 bar, 3.45 kPa) - well above the operating set-point range, providing headroom for transient pressure spikes from damper slams or fan start-up surges.
Tested to 6,000 cycles minimum at 0.5 psi maximum pressure each cycle and at maximum electrical load (UL-recognized mechanical endurance test). The 100,000-cycle rating on auto-reset SPDT variants reflects the lighter mechanical stress from snap-back operation, while the 6,000-cycle rating on manual-reset variants reflects the heavier mechanical action of the reset mechanism plus higher inductive ratings on the contacts.
Technical Specifications
| Specification | Detail |
|---|---|
| Product Type | Differential air pressure switch, snap-acting |
| Input Pressure Range | 0.4-12 inWC (+/-0.06 inWC tolerance on AFS-460 series, +/-0.02 inWC on AFS-222/262) |
| Set Point Range | 0.4-12 inWC |
| Field-Adjustable Operate Range | 0.46 to 12.0 inWC |
| Field-Adjustable Release Range | 0.46 to 11.2 inWC |
| Switching Differential | Progressive, increasing from minimum set point to 0.8 inWC at maximum set point |
| Contact Arrangement | SPST-NC |
| Contact (Load) Rating | 15A at 125, 250, or 277 VAC; 1/2A at 125 VDC; 1/4A at 250 VDC; 1/4 hp at 125 VAC; 1/2 hp at 250 VAC |
| Reset Style | Manual |
| Measured Media | Air |
| Maximum Pressure | 0.5 psi (0.03 bar, 3.45 kPa) |
| Life Expectancy | 6,000 cycles minimum at 0.5 psi maximum pressure each cycle and at maximum electrical load (UL-recognized mechanical endurance test) |
| Operating Temperature | -40 to 180 deg F (-40 to 82 deg C) |
| Operating Humidity | 10-95% RH non-condensing |
| Mounting Direction | Diaphragm in any vertical plane (required for lowest set point) |
| Enclosure Material | Galvanized steel, plated |
| Sample Line Connections | 1/4 inch OD rigid or semi-rigid metallic tubing (integral compression ferrule and nut) |
| Electrical Connections | Screw-top terminals with cup washers |
| Conduit Opening | 7/8 inch diameter opening accepts 1/2 inch conduit |
| Agency Approvals | UL, CSA, CE |
| Dimensions (H x W x D) | 6.25 x 4.46 x 3.18 in (158.8 x 113.3 x 80.8 mm) |
| Weight | 1.2 lb (0.544 kg) |
| Mounting Hole Spacing | 3-7/8 in (98.55 mm) apart, 3/16 in diameter holes |
| Calibration Adjustment | 1.16 inWC per full turn (10 calibration turns total) |
| Manufacturer | ACI (Automation Components, Inc.) - Middleton, WI USA |
| Manufacturer Part Number | AFS-460 |
| Item Number | 101791 |
| Warranty | 2-Year ACI Limited Warranty |
What's In the Box
- AFS switch with plated galvanized-steel housing, factory-set to a nominal mid-range set point
- Integral mounting bracket (3/16" holes, 3-7/8" apart)
- Installation & Operation Instructions
- Integral compression fittings (ferrule and nut, factory-installed)
- Manual reset button (operator must press to re-arm after each trip)
- Sample-line tubing - 1/4" OD rigid or semi-rigid metallic tubing for compression fitting
- Slip-on adapter for flexible tubing - ACI P/N 18311 (suitable for slipping on 1/4" flexible plastic tubing if you want to use flexible tubing with the compression-fitting model)
- Sampling pitot tubes for in-duct pressure pickup: PT 3", PT 5.2", PT 7.5", PT 9.7" (foam-gasket, multi-point); SPT-3.5" / SPT-8.0" (aluminum, flat tip, static); VPT / VPT-8" (aluminum, pointed tip, velocity)
- Pickup ports for wall/room pressure taps: A/SP-PUP, A/R-PUP, A/R2-PUP, A/O-PUP-H, A/O-PUP-V
- 1/2" conduit fitting and conduit (if used)
- Wire (14-22 AWG appropriate for the contact load) and disconnect/fuse per local code
Documentation
Frequently Asked Questions
What is the AFS-460 used for?
The AFS-460 is a general-purpose differential air pressure switch used in HVAC and Energy Management applications for monitoring filter blockage, proof of flow, prove excessive or insufficient flow, alarms and control. The snap-acting contact closes (or opens) when the differential pressure across the sensing diaphragm exceeds the set point - giving a binary "pressure OK / not OK" signal to a BAS controller, alarm panel, or interlock circuit. Can sense positive, negative, or differential air pressure depending on how the sample lines are connected.
What is the set point range and how do I adjust it?
The set point range is 0.4-12 inWC, adjustable in the field via the on-board adjustment screw. Procedure: turn the adjustment screw counterclockwise until motion stops, then turn 4 complete turns clockwise to engage the calibration spring; the next 10 turns are the active calibration range. Each full turn represents approximately 1.16 inWC per full turn (10 calibration turns total). Use a digital manometer or other measuring device to confirm the actual set point during calibration - the turn-count is a starting reference, not a precision calibration.
What's the difference between manual and automatic reset?
Manual reset (this SKU): after the switch trips, it stays in the tripped state until the operator presses the reset button on the enclosure - required for safety-critical applications where the system must NOT auto-recover after a fault (fan-failure shutdowns, freeze-protection lockouts, filter-replacement alarms). Automatic reset (the AFS-222 and AFS-262 variants): the switch resets itself when pressure returns to the normal range - appropriate for continuous monitoring applications where transient excursions are expected and don't require operator intervention.
Why does the switch need to be mounted vertically?
The diaphragm must be in a vertical plane to achieve the lowest specified operating set point. Mounting horizontal puts gravity load on the diaphragm that biases the trip point and prevents the switch from reaching its lowest rated operate range. Also avoid mounting with the sample-line connections pointing upward - condensate will accumulate in the tubing and affect both response time and trip-point accuracy. Surface-mount via the two 3/16" diameter holes in the integral mounting bracket; the holes are 3-7/8" apart center-to-center.
What sample-line tubing should I use?
This switch accepts 1/4" OD rigid or semi-rigid metallic tubing via the integral compression fittings (ferrule and nut). Tubing length guidelines: for sample lines up to 10 feet, 1/4" OD tubing is acceptable; for lines up to 20 feet, use 1/4" ID tubing; for runs from 20-60 feet, step up to 1/2" ID tubing to avoid degrading the response time. ACI offers medical-grade tubing kits in various lengths: A/10' TUBE, A/20' TUBE, A/50' TUBE, A/100' TUBE. Locate the sampling probe a minimum of 1.5 duct diameters downstream from the air source, as close to the center of the airstream as practical.
Which inlet do I connect to - high or low?
Positive pressure only: connect the sample line to inlet H (high); leave inlet L (low) open to atmosphere. Negative pressure only: connect to inlet L; leave inlet H open to atmosphere. Two negative samples: higher negative sample to inlet L, lower negative sample to inlet H. Two positive samples: higher positive sample to inlet H, lower positive sample to inlet L. One positive and one negative sample: positive to inlet H, negative to inlet L. The pressure DIFFERENCE between H and L is what drives the diaphragm.
What accessories do I need for installation?
Required: sample-line tubing (specified above), 14-22 AWG wire appropriate for the contact load, and 1/2" conduit if your install requires conduit routing. Application-dependent: sampling pitot tubes for in-duct pressure pickup (PT 3", PT 5.2", PT 7.5", PT 9.7" foam-gasket; SPT-3.5", SPT-8.0" aluminum static flat tip; VPT, VPT-8" aluminum velocity pointed tip), or pickup ports for wall/room pressure taps (A/SP-PUP stainless, A/R-PUP beige, A/R2-PUP white, A/O-PUP-H / A/O-PUP-V outdoor weatherproof). Keep sample-line runs as short as practical for fastest response time.
What media is this switch compatible with?
Air. The diaphragm is NOT compatible with: liquids of any kind, refrigerants, corrosive gases (chlorine, ammonia, hydrogen sulfide, acid fumes), or media that will degrade silicone elastomers. Maximum overpressure tolerance is 0.5 psi (3.45 kPa); exceeding this will damage the diaphragm and can cause permanent set-point drift or complete failure. For liquid-pressure switching, see Belimo's wet/wet differential pressure switches in the Liquid Pressure subcategory.
What agency approvals does this switch carry?
This switch is UL, CSA, CE approved. The UL listing covers the mechanical endurance test of the snap-acting switch mechanism and the electrical isolation between the contact circuit and the diaphragm-sensing portion of the device. For mission-critical safety applications (life-safety smoke control, fire-suppression interlocks), verify the specific agency listings required by your local AHJ - this switch is a general-purpose proving switch, not a UL864 life-safety device.
What's the warranty?
2-Year ACI Limited Warranty - covers manufacturing defects in materials and workmanship under normal use. The full warranty terms are in the front of ACI's Sensors & Transmitters catalog at workaci.com. Manufactured in Middleton, Wisconsin, USA. ZOT Supply is an authorized ACI distributor; warranty claims are processed directly with ACI.
- Series:
- AFS
- Pressure Range:
- 0.4-12 inWC
- Range Class:
- Medium
- Contact Style:
- SPST-NC
- Reset Style:
- Manual
- Sample Line Fitting:
- Compression (1/4 in OD rigid)
- Maximum Pressure:
- 0.5 psi (3.45 kPa)
- Approvals:
- UL, CSA, CE
- Mounting:
- Any vertical plane
- Made in USA:
- Yes