The Belimo NFX24-MFT-S is a spring return fail-safe damper actuator with 90 in-lb [10 Nm] of motor torque. It runs on AC/DC 24 V nominal voltage with MFT/programmable control and a 2 to 10 V default operating range. It has 2x SPDT auxiliary switches and a NEMA 2 degree of protection.
Specifications sourced from the Belimo NFX24-MFT-S technical data sheet (en-us, 2026-10-20).
Best for
- Damper control that needs 90 in-lb [10 Nm] of torque
- Applications that require a fail-safe position on loss of power
- Jobs that need a programmable (MFT) control input
- Air plenum installations (UL 2043 compliant)
- Signaling or interlock circuits using the built-in 2x SPDT auxiliary switches
Key Features
90 in-lb Torque
Motor torque of 90 in-lb [10 Nm]. Angle of rotation: 95°.
Spring Return Fail-Safe
Fail-safe running time: <20 s @ -20 to 50°C, <60 s @ -30°C. Direction of fail-safe motion: reversible with cw/ccw mounting.
MFT Programmable Control
Operating range Y: 2 to 10 V (4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)). Variable operating range: Start point 0.5 to 30 V End point 2.5 to 32 V. Optional operating modes: variable (VDC, PWM, on/off, floating point). Position feedback U: 2 to 10 V.
2x SPDT Auxiliary Switch
Auxiliary switch: 2x SPDT, 1 mA to 3 A (0.5 A inductive), DC 5 V to AC 250 V, 1x 10% / 1x 11 to 90%.
NEMA 2 Enclosure
Degree of protection NEMA/UL: NEMA 2. Housing: UL Enclosure Type 2. UL 2043 compliant: Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC.
Running Time and Override
Motor running time: 150 s / 90°. Variable running time: 40 to 150 s. Manual override: 5 mm hex crank (3/16" Allen), supplied.
ZOT Supply is an authorized distributor of Belimo products.
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Belimo |
| Part Number | NFX24-MFT-S |
| Nominal Voltage | AC/DC 24 V |
| Nominal Voltage Frequency | 50/60 Hz |
| Nominal Voltage Range | AC 19.2 to 28.8 V / DC 21.6 to 28.8 V |
| Power Consumption in Operation | 6.5 W |
| Power Consumption in Rest Position | 3 W |
| Transformer Sizing | 9 VA |
| Auxiliary Switch | 2x SPDT, 1 mA to 3 A (0.5 A inductive), DC 5 V to AC 250 V, 1x 10% / 1x 11 to 90% |
| Switching Capacity Auxiliary Switch | 1 mA to 3 A (0.5 A inductive), DC 5 V to AC 250 V |
| Electrical Connection | (2) 18 AWG appliance cables, 1 m, 3 m or 5 m, with or without 1/2" NPT conduit connectors |
| Overload Protection | electronic throughout 0 to 95° rotation |
| Electrical Protection | actuators are double insulated |
| Torque Motor | 90 in-lb [10 Nm] |
| Operating Range Y | 2 to 10 V |
| Operating Range Y Note | 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor) |
| Input Impedance | 100 kΩ for 2 to 10 V (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, On/Off and Floating point |
| Operating Range Y Variable | Start point 0.5 to 30 V End point 2.5 to 32 V |
| Operating Modes Optional | variable (VDC, PWM, on/off, floating point) |
| Position Feedback U | 2 to 10 V |
| Position Feedback U Note | Max. 0.5 mA |
| Position Feedback U Variable | VDC variable |
| Direction of Motion Motor | selectable with switch 0/1 |
| Direction of Motion Fail-Safe | reversible with cw/ccw mounting |
| Manual Override | 5 mm hex crank (3/16" Allen), supplied |
| Angle of Rotation | 95° |
| Angle of Rotation Note | adjustable with mechanical end stop, 35 to 95° |
| Running Time (Motor) | 150 s / 90° |
| Running Time Motor Variable | 40 to 150 s |
| Running Time Fail-Safe | <20 s @ -20 to 50°C, <60 s @ -30°C |
| Sound Power Level Motor | 40 dB(A) |
| Sound Power Level, Fail-Safe | 62 dB(A) |
| Adaptation Setting Range | off (default) |
| Override Control | MIN (minimum position) = 0% MID (intermediate position) = 50% MAX (maximum position) = 100% |
| Position Indication | Mechanical |
| Power Source UL | Class 2 Supply |
| Degree of Protection NEMA/UL | NEMA 2 |
| Housing | UL Enclosure Type 2 |
| Agency Listing | cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02 CE acc. to 2014/30/EU and 2014/35/EU |
| Quality Standard | ISO 9001 |
| UL 2043 Compliant | Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC |
| Ambient Humidity | Max. 95% RH, non-condensing |
| Ambient Temperature | -22 to 122°F [-30 to 50°C] |
| Storage Temperature | -40 to 176°F [-40 to 80°C] |
| Servicing | maintenance-free |
| Weight | 4.9 lb [2.2 kg] |
| Housing Material | UL94-5VA |
| Notes | Variable when configured with MFT options. Rated Impulse Voltage 800V, Type of Action 1.AA.B, Control Pollution Degree 3. |
| Warranty | 5 years |
Documentation
Related Options
Other Actuator Models
Accessories
Tools
Electrical Accessories
Mechanical Accessories
Frequently Asked Questions
What is the Belimo NFX24-MFT-S?
The Belimo NFX24-MFT-S is a spring return fail-safe damper actuator with 90 in-lb [10 Nm] of motor torque. It runs on AC/DC 24 V nominal voltage with MFT/programmable control and a 2 to 10 V default operating range. It has 2x SPDT auxiliary switches and a NEMA 2 degree of protection.
What power supply does the NFX24-MFT-S need?
The NFX24-MFT-S has a nominal voltage of AC/DC 24 V at 50/60 Hz, with a nominal voltage range of AC 19.2 to 28.8 V / DC 21.6 to 28.8 V. Power consumption is 6.5 W in operation and 3 W in rest position. Transformer sizing: 9 VA.
What control signal does the NFX24-MFT-S use?
The NFX24-MFT-S uses MFT Programmable control. Operating range note: 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor). The operating range Y is 2 to 10 V. Input impedance: 100 kΩ for 2 to 10 V (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, On/Off and Floating point. Position feedback U: 2 to 10 V.
How much torque does the NFX24-MFT-S provide?
The NFX24-MFT-S delivers 90 in-lb [10 Nm] of motor torque. Angle of rotation: 95° (adjustable with mechanical end stop, 35 to 95°).
Is the NFX24-MFT-S a fail-safe actuator?
Yes. The NFX24-MFT-S is a fail-safe actuator with a fail-safe running time of <20 s @ -20 to 50°C, <60 s @ -30°C. Direction of fail-safe motion: reversible with cw/ccw mounting.
What is the running time of the NFX24-MFT-S?
Motor running time is 150 s / 90°. Variable running time: 40 to 150 s.
Does the NFX24-MFT-S have an auxiliary switch?
Yes. Auxiliary switch: 2x SPDT, 1 mA to 3 A (0.5 A inductive), DC 5 V to AC 250 V, 1x 10% / 1x 11 to 90%.
What is the enclosure rating of the NFX24-MFT-S?
The NFX24-MFT-S has a NEMA 2 degree of protection (UL Enclosure Type 2). UL 2043 compliant: Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC. Ambient temperature: -22 to 122°F [-30 to 50°C]. Ambient humidity: Max. 95% RH, non-condensing.
- Actuator Type:
- Fail-Safe
- Torque / Force:
- 90 in-lb
- Control Signal:
- Programmable (MFT)
- Voltage:
- 24 VAC/DC
- Auxiliary Switch:
- 2x SPDT
- Enclosure:
- NEMA 2
- Series:
- NF
- Feedback Signal:
- 2-10 VDC