PS3FX-R-D-N — PowerScout FLEX 3 Multi-Circuit Power Submeter
The Dent Instruments PS3FX-R-D-N is part of the PowerScout™ FLEX 3 family, DENT's next-generation three-channel multi-circuit submeter that replaces the PowerScout™ HD. The PS3FX-R-D-N measures voltage, current, power, energy, and a wide range of electrical parameters on any combination of single- and three-phase loads, making it well suited to tenant submetering, bi-directional (import/export) metering, and real-time energy monitoring across commercial and industrial facilities.
The PS3FX-R-D-N delivers revenue-grade performance with continuous 7.2 kHz sampling (no blind cycles), a 1-second parameter update rate, and ANSI C12.1-2024 Class 0.2 accuracy when paired with an appropriate CT. It supports both BACnet and Modbus, and every FLEX 3 model — including this PS3FX-R-D-N — provides RS-485 serial and 10/100 Ethernet as standard. Setup is handled through FLEXPoint™ PC software or the browser-based FLEXPoint™ GO web server, and DENT's patented PhaseChek™ circuitry confirms correct CT orientation during commissioning.
Housed in a compact DIN rail enclosure that drops into the external enclosure of your choice (UL 94-V0 ABS), the PS3FX-R-D-N is delivered in the DIN Rail Mount Enclosure form factor. Like all PowerScout meters, the PS3FX-R-D-N is designed to operate as an endpoint that reports to a building management system, RTU, or data acquisition device rather than as a standalone recorder.
Best for
- Tenant and accountability submetering in commercial, retail, and mixed-use buildings
- Bi-directional metering for solar, wind, and other renewable or storage interconnections
- Monitoring building mains, HVAC, pumps, motors, and equipment loads
- Multi-circuit measurement using Virtual Meters to group the PS3FX-R-D-N's three channels by load
- Hospitals, data centers, and government projects requiring BAA / TAA compliant equipment
Key Features
FLEXPoint™ + FLEXPoint™ GO
Configure the PS3FX-R-D-N from a rebuilt PC application or directly from any web browser with FLEXPoint GO — no software install required for on-site changes, validation, and field troubleshooting.
Flexible Virtual Meters
Assign any of the three CT channels to any load in any combination — single-phase, split-phase, or three-phase groupings — and meter multiple loads from a single PS3FX-R-D-N with consistent load labels across software, register exports, and cloud systems.
Dual-Protocol, Serial + Ethernet
The PS3FX-R-D-N speaks both BACnet and Modbus and includes RS-485 serial and 10/100 Ethernet on every model, with an IEEE-754 floating-point register map that eliminates scaling factors and flattens Virtual Meters to a single address.
PhaseChek™ + Revenue-Grade Accuracy
Built-in PhaseChek verification confirms correct CT orientation and phase matching to reduce installation errors, while the PS3FX-R-D-N meets ANSI C12.1-2024 Class 0.2 revenue-grade accuracy (dependent on CT selection).
Universal CT Compatibility
Mix and match a full range of 333.3 mV CTs — Solid Core, Split Core, or RōCoil™ (Rogowski) — including revenue-grade options, measuring up to 4000+ A depending on the CT used with the PS3FX-R-D-N.
BAA & TAA Compliant
DENT Instruments marks the PowerScout FLEX 3 Buy American Act (BAA) and TAA compliant, supporting procurement requirements common to government, healthcare, and institutional projects.
Technical Specifications
| Specification | PS3FX-R-D-N |
|---|---|
| Model / Part Number | PS3FX-R-D-N |
| Series | PowerScout FLEX 3 (3-channel, multi-circuit) |
| Service Type | Single Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
| Power | From L1 Phase to L2 Phase. 90-600 VAC RMS, CAT III, 50/60 Hz, 500 mA AC Max |
| AC Protection | 0.5 A internal fuse protection; 200 kA interrupt |
| Voltage Channels | 80-346 VAC Line-to-Neutral, 600 V Line-to-Line, CAT III |
| Current Channels | 3 channels, 0.525 VAC max, 333.3 mV CTs, 0-4000+ A depending on CT |
| Maximum Current Input | 150% of CT rating (mV CTs) to maintain accuracy; up to 4000 A with RōCoil CTs |
| Measurement Type | True RMS using high-speed digital signal processing (DSP) |
| Accuracy | 0.2% — ANSI C12.1-2024 Class 0.2; NIST traceable calibration |
| Resolution | 32-bit floating point (IEEE-754) |
| Line Frequency | 50/60 Hz (45-65 Hz measurable range); measured L1-N |
| Sampling | Continuous 7.2 kHz (no blind cycles) |
| Parameter Update Rate | 1.0 second |
| Measurements | Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import/Export/Net kWh, kVAh and kVARh, THD, Theta, Frequency — per phase and per Virtual Meter |
| Display | 2 x 16-character LCD with tri-color backlight |
| Communications Hardware | RS-485 Serial and 10/100 Ethernet |
| Supported Protocols | Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP |
| Communication Rate | Modbus: 9600-115200 baud; BACnet: 9600-76800 baud |
| Max Communication Length | 1200 m at 100K bits/second or less |
| Alarm Output | Undervoltage (open collector, 30 VDC max) |
| USB | USB 2.0 (USB-C) |
| Web Page Security | 2 levels of PIN protection (Read/Write or Read-Only) |
| Mounting | TS35/7.5 DIN rail |
| Enclosure | ABS plastic, 94-V0 flammability rating |
| Enclosure Dimensions | 19.08 x 8.23 x 3.76 cm (7.51 x 3.24 x 1.48 in) |
| Weight (approximate) | 363 g (13 oz), excluding CTs |
| Wire Connections | 12-28 AWG, 600 VAC; voltage connection must be #14 AWG or larger and 600 VAC rated |
| Operating Temperature | -20 to 60 °C (-4 to 140 °F). At -20 °C the LCD may be difficult to read and supply voltage must exceed 100 VAC; colder temperatures require higher supply voltage |
| Humidity | 5% to 95% non-condensing |
| Certifications | UL Listed (UL 61010-1 3rd Ed. & IEC 61010-2-030); CE (LVD EN61010-1, EMC EN61326-1); RoHS 3 (IEC 63000:2018); Buy American Act (BAA) and TAA compliant |
| Configuration Software | FLEXPoint™ (Windows 10 / 11) and FLEXPoint™ GO web server |
Specifications verified against the DENT Instruments PowerScout FLEX 3 datasheet, revision 01/26/2026. Manufacturer specifications are subject to change.
Documentation
- PDF PowerScout FLEX 3 Data Sheet
- PDF Installation, Wiring & Operator's Guide
- PDF FLEXPoint Software & Integration Guide
- PDF Commissioning Checklist
- PDF Quick Start Guide
Frequently Asked Questions
What protocols does the PS3FX-R-D-N support?
The PS3FX-R-D-N supports Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP, so it can integrate with most BACnet or Modbus building management and energy systems.
Does the PS3FX-R-D-N include both serial and Ethernet?
Yes. Every PowerScout FLEX 3 model, including the PS3FX-R-D-N, ships with RS-485 serial and 10/100 Ethernet as standard.
Which current transformers work with the PS3FX-R-D-N?
The PS3FX-R-D-N accepts 333.3 mV DENT CTs — Solid Core, Split Core, and RōCoil™ (Rogowski) — including revenue-grade options, and measures up to 4000+ A depending on the CT selected.
What is the form factor of the PS3FX-R-D-N?
The PS3FX-R-D-N is supplied in the DIN Rail Mount Enclosure (compact DIN rail enclosure that drops into the external enclosure of your choice), measuring 19.08 x 8.23 x 3.76 cm (7.51 x 3.24 x 1.48 in).
Is the PS3FX-R-D-N revenue grade?
The PS3FX-R-D-N meets ANSI C12.1-2024 Class 0.2 revenue-grade accuracy, dependent on the CT selected, and ships with a NIST-traceable calibration.
How does the PS3FX-R-D-N get data to a host or BMS?
The PS3FX-R-D-N operates as an endpoint, reporting over Ethernet (BACnet/IP or Modbus TCP) or RS-485 (Modbus RTU or BACnet MS/TP) to a building management system, RTU, or data acquisition device.
Is the PS3FX-R-D-N BAA and TAA compliant?
Yes. DENT Instruments marks the PowerScout FLEX 3 Buy American Act (BAA) and TAA compliant, supporting government and institutional procurement. Contact ZOT Supply if you need compliance documentation for a procurement file.
Warranty
This PowerScout Series meter is covered by DENT Instruments’ five-year (60-month) limited warranty from the invoice date. Warranty service requires an RMA and is subject to DENT’s current warranty terms — see the DENT Instruments warranty statement. Supplied by ZOT Supply, an authorized DENT Instruments distributor.
- Product Line:
- PowerScout FLEX
- Revenue Grade:
- Yes
- Accuracy Class:
- ANSI C12.1 Class 0.2
- Communication:
- Modbus RTU
- Communication:
- BACnet MS/TP
- Current Input:
- 333 mV
- Current Input:
- Rogowski
- Mounting:
- DIN Rail