Prolon PL-M2000-CHL : Chiller Controller, Up To 4 Chiller Stages, Outdoor Reset, Pump VFD Control, 9 Analog Inputs, 5 Triac Outputs, 3 Analog Outputs, Modbus RTU (RS485)

Prolon

Your Price:  $1,341.71
(No reviews yet) Write a Review
SKU:
PL-M2000-CHL
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
Controller TypeChiller Controller
Inputs9 analog inputs
Digital Outputs5 triac, 10-30 VAC source
Analog Outputs3 x 0-10 VDC, 40 mA max
ProtocolModbus RTU (RS485)
Supply24 VAC, Class 2
The Prolon PL-M2000-CHL is a Modbus RTU chiller controller for air cooled and water cooled chillers, staging up to 4 chillers, resetting chilled water supply temperature, and modulating a VFD on each pump to hold a fixed water pressure setpoint.

Specifications sourced from Prolon datasheet PL-DATA-M2000CHL-C/F-EN, REV 7.3.4. Verified September 18, 2026.

Overview

The M2000 CHL is a chiller plant controller for both air cooled and water cooled chillers. It stages chillers, rotates pumps and chillers on lead-lag, and resets the chilled water supply setpoint from outside air temperature, return temperature, or demand. Condenser water limits can lock out or stage down the chillers. Nine analog inputs are individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC signals, and sequences are configured locally or remotely with the free Prolon Focus software.

Best For

  • Air cooled or water cooled chiller plants staging up to 4 chillers
  • Plants with VFD driven pumps held to a fixed water pressure setpoint
  • Systems requiring condenser water lockout or stage-down protection
  • Chilled water plants that need Modbus RTU integration without a proprietary supervisor

Warranty and Sourcing

ZOT Supply is an authorized Prolon distributor. Every PL-M2000-CHL ships new in factory packaging and is covered by the Prolon manufacturer warranty. For current warranty terms and RMA handling, contact ZOT Supply at 855-825-2811 or sales@zotsupply.com.

Key Features

Up to 4 chiller stages

Stages multiple chillers, a single multistage chiller, or a combination of both.

Pump VFD control

Modulates a VFD for each pump to maintain a fixed water pressure setpoint.

Condenser water protection

Locks out or stages down chillers on entering or leaving condenser water temperature limits.

Flexible setpoint reset

Resets the supply water setpoint from outside temperature, return temperature, or demand.

Lead-lag rotation

Multiple lead-lag sequences are available for both the pumps and the chillers.

Pump disable input

A dedicated input deactivates the pumps on contact closure.

  • Pump activity based on outside temperature or schedule (or both)
  • Configurable pump exercise sequence for extended periods of inactivity
  • Internal clock with configurable schedules and calendars
  • A manual/off/auto switch for each of the eight outputs
  • 5 digital outputs and 3 analog outputs equipped with resettable fuses
  • Built-in protection sequences with configurable temperature limits and minimum delays

Technical Specifications

SpecificationPL-M2000-CHL
Supply24 VAC +/-10%, 50/60 Hz, Class 2
Power5 VA (consumption), 40 VA (input)
Inputs9 analog inputs (outside temp / supply water temp / return water temp / dry contacts for proof of pumps, entering condenser water temp, leaving condenser water temp, water pressure and alarm). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
MicroprocessorPIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
Dimensions5.39 in x 4.41 in x 2.25 in (137 mm x 112 mm x 57 mm)
Weight1.05 lbs (0.48 kg)
Environment-4 to 122 °F (-20 to 50 °C) Non-Condensing
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Documentation

Frequently Asked Questions

Does the PL-M2000-CHL work with air cooled and water cooled chillers?

Yes. The M2000 CHL is designed for both air cooled and water cooled chiller systems, and it can lock out or stage down chillers based on entering or leaving condenser water temperature limits.

Can the PL-M2000-CHL control pump VFDs?

Yes. It can modulate a VFD for each pump to maintain a fixed water pressure setpoint, using one of the 3 analog 0-10 VDC outputs.

How many chiller stages does the PL-M2000-CHL support?

Up to 4 chiller stages, covering multiple chillers, a single multistage chiller, or a combination, with lead-lag sequences for both pumps and chillers.

What input signal types does the PL-M2000-CHL accept?

Each of the 9 analog inputs is individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.

How does the PL-M2000-CHL communicate?

Modbus RTU over RS485, up to 127 nodes, at 9600 through 115200 baud. Connections are removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks.

Controller Type:
Chiller
Digital Outputs:
5
Analog Outputs:
3
Inputs:
9
Communication:
Modbus RTU (RS485)