Specifications sourced from Prolon datasheet PL-DATA-M2000MUA-C/F-EN, REV 7.3.0. Verified September 18, 2026.
Overview
The M2000 MUA controls make-up air units in single, dual, or variable volume configurations, with separate configurable winter and summer sequences. Discharge air temperature is reset from outside air temperature or zone demand, and a variable frequency drive can be modulated to hold building pressure or a CO2 setpoint. Nine analog inputs cover zone, outside, and discharge temperatures plus dry contacts for proof of exhaust, fan and damper opening, manual overrides, CO2 levels, and static pressure. Safety limits and a lockout mode are built in.
Best For
- Single, dual, or variable volume make-up air units
- Kitchen and process exhaust replacement air with proof of exhaust interlocks
- Buildings holding a pressure or CO2 setpoint through a VFD
- Units needing separate winter and summer sequences
Warranty and Sourcing
Key Features
Single, dual, or variable volume
Three volume sequences are available for the unit.
Winter and summer sequences
Winter and summer sequences are configured separately.
Discharge air reset
Discharge air temperature is reset from outside temperature or zone demand.
Building pressure or CO2 VFD control
A variable frequency drive is modulated for building pressure control or CO2 control.
Proof of exhaust interlocks
Dry contact inputs cover proof of exhaust, fan and damper opening, and manual overrides.
Lockout override
A manual input deactivates lockout mode.
- Internal clock with configurable schedules and calendars
- A manual/off/auto switch for each of the eight outputs
- Stand-alone or networked (up to 127 nodes)
- Proportional integral (PI) control loops
- 5 digital outputs and 3 analog outputs equipped with resettable fuses
- Built-in protection sequences with configurable temperature limits and minimum delays
Technical Specifications
| Specification | PL-M2000-MUA |
|---|---|
| Supply | 24 VAC +/-10%, 50/60 Hz, Class 2 |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 9 configurable analog inputs (zone temp / outside temp / discharge temp, dry contact for proof of exhaust, fan and damper opening, manual overrides, CO2 levels, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Microprocessor | PIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks |
| Dimensions | 5.39 in x 4.41 in x 2.25 in (137 mm x 112 mm x 57 mm) |
| Weight | 1.05 lbs (0.48 kg) |
| Environment | -4 to 122 °F (-20 to 50 °C) Non-Condensing |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
Documentation
Frequently Asked Questions
Can the PL-M2000-MUA control building pressure?
Yes. It performs building pressure control or CO2 control using a variable frequency drive, driven from one of the 3 analog 0-10 VDC outputs.
What volume sequences does the PL-M2000-MUA support?
Single, dual, or variable volume sequences, with separately configurable winter and summer sequences.
How does the PL-M2000-MUA reset discharge air temperature?
Discharge air temperature is reset based on outside temperature or on zone demand.
What inputs does the PL-M2000-MUA provide?
9 configurable analog inputs covering zone temp, outside temp, and discharge temp, plus dry contacts for proof of exhaust, fan and damper opening, manual overrides, CO2 levels, and static pressure.
What input signal types does the PL-M2000-MUA accept?
Each input is individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.
- Controller Type:
- Make Up Air
- Digital Outputs:
- 5
- Analog Outputs:
- 3
- Inputs:
- 9
- Communication:
- Modbus RTU (RS485)
- Product Series:
- M2000