Specifications sourced from Prolon datasheet PL-DATA-M2000HP-C/F-EN, REV 7.3.1. Verified September 18, 2026.
Overview
The M2000 HP controls air-to-air and water-to-air heat pump units, with the mode selected in configuration rather than in hardware. It stages up to 2 compressors and 2 auxiliary heating stages, and adds economizer, preheating, emergency auxiliary heating, and static pressure functions. On a Prolon network it acts as a master controller, and its FlexiZone system manages multiple zones by evaluating the average weighted demand of customized zone groups. All 9 analog inputs are individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.
Best For
- Air-to-air or water-to-air heat pump units, selectable in configuration
- Heat pumps with 2 compressor stages and 2 stages of auxiliary heat
- Zoned systems where the rooftop unit acts as the FlexiZone master
- Units that need economizer, preheat, or static pressure sequences on board
Warranty and Sourcing
Key Features
Air-to-air or water-to-air
Configurable to run in either air-to-air or water-to-air mode.
2 compressor stages
Controls up to 2 compressor stages and 2 stages of auxiliary heating.
FlexiZone master
Manages multiple zones by evaluating the average weighted demand of customized zone groups.
Network master
Acts as a master controller when connected to a Prolon network.
Economizer and preheat
Economizer, preheating, emergency auxiliary heating, and static pressure functions are available.
Configurable inputs
9 analog inputs individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.
- Internal clock with configurable schedules and calendars
- Configurable unoccupied mode sequences
- A manual/off/auto switch for each of the eight outputs
- Proportional-Integral (PI) control loops
- 5 digital outputs and 3 analog outputs equipped with resettable fuses
- Built-in protection sequences with configurable temperature limits and minimum delays
Technical Specifications
| Specification | PL-M2000-HP |
|---|---|
| Supply | 24 VAC +/-10%, 50/60 Hz, Class 2 |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 9 configurable analog inputs (outside temperature / return / supply / zone / water supply / dry contact for clogged filter / schedule override / proof of fan / alarm, room setpoint, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Microprocessor | PIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks |
| Dimensions | 5.39 in x 4.41 in x 2.25 in (137 mm x 112 mm x 57 mm) |
| Weight | 1.05 lbs (0.48 kg) |
| Environment | -4 to 122 °F (-20 to 50 °C) Non-Condensing |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
Documentation
Frequently Asked Questions
Does the PL-M2000-HP work with water source heat pumps?
Yes. It is configurable to run in air-to-air mode or water-to-air mode, and the input list includes a water supply temperature point.
How many compressor stages does the PL-M2000-HP control?
Up to 2 compressor stages, plus 2 stages of auxiliary heating.
Can the PL-M2000-HP act as a network master?
Yes. It acts as a master controller when connected to a Prolon network, and its FlexiZone system manages multiple zones by evaluating the average weighted demand of the zones using customized groups.
What input signal types does the PL-M2000-HP accept?
Each of the 9 analog inputs is individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.
What outputs does the PL-M2000-HP provide?
5 triac digital outputs rated 10-30 VAC source, 300 mA max with a resettable fuse, plus 3 analog outputs at 0-10 VDC, 40 mA max. Each of the eight outputs has a manual/off/auto switch.
- Controller Type:
- Heat Pump
- Digital Outputs:
- 5
- Analog Outputs:
- 3
- Inputs:
- 9
- Communication:
- Modbus RTU (RS485)
- Product Series:
- M2000