null Skip to main content

Prolon PL-M2000-HP : Heat Pump Controller, Air-To-Air or Water-To-Air, 2 Compressor Stages, FlexiZone Master, Economizer, 9 Configurable Analog Inputs, 5 Triac Outputs, 3 Analog Outputs, Modbus RTU (RS485)

Prolon

Your Price:  $1,341.71
(No reviews yet) Write a Review
SKU:
PL-M2000-HP
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
Controller TypeHeat Pump Controller
Inputs9 configurable analog inputs
Digital Outputs5 triac, 10-30 VAC source
Analog Outputs3 x 0-10 VDC, 40 mA max
ProtocolModbus RTU (RS485)
Supply24 VAC, Class 2
The Prolon PL-M2000-HP is a Modbus RTU heat pump controller that runs in air-to-air or water-to-air mode, stages 2 compressors and 2 auxiliary heating stages, and acts as a FlexiZone master on a Prolon network.

Specifications sourced from Prolon datasheet PL-DATA-M2000HP-C/F-EN, REV 7.3.1. Verified September 18, 2026.

Overview

The M2000 HP controls air-to-air and water-to-air heat pump units, with the mode selected in configuration rather than in hardware. It stages up to 2 compressors and 2 auxiliary heating stages, and adds economizer, preheating, emergency auxiliary heating, and static pressure functions. On a Prolon network it acts as a master controller, and its FlexiZone system manages multiple zones by evaluating the average weighted demand of customized zone groups. All 9 analog inputs are individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.

Best For

  • Air-to-air or water-to-air heat pump units, selectable in configuration
  • Heat pumps with 2 compressor stages and 2 stages of auxiliary heat
  • Zoned systems where the rooftop unit acts as the FlexiZone master
  • Units that need economizer, preheat, or static pressure sequences on board

Warranty and Sourcing

ZOT Supply is an authorized Prolon distributor. Every PL-M2000-HP ships new in factory packaging and is covered by the Prolon manufacturer warranty. For current warranty terms and RMA handling, contact ZOT Supply at 855-825-2811 or sales@zotsupply.com.

Key Features

Air-to-air or water-to-air

Configurable to run in either air-to-air or water-to-air mode.

2 compressor stages

Controls up to 2 compressor stages and 2 stages of auxiliary heating.

FlexiZone master

Manages multiple zones by evaluating the average weighted demand of customized zone groups.

Network master

Acts as a master controller when connected to a Prolon network.

Economizer and preheat

Economizer, preheating, emergency auxiliary heating, and static pressure functions are available.

Configurable inputs

9 analog inputs individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.

  • Internal clock with configurable schedules and calendars
  • Configurable unoccupied mode sequences
  • A manual/off/auto switch for each of the eight outputs
  • Proportional-Integral (PI) control loops
  • 5 digital outputs and 3 analog outputs equipped with resettable fuses
  • Built-in protection sequences with configurable temperature limits and minimum delays

Technical Specifications

SpecificationPL-M2000-HP
Supply24 VAC +/-10%, 50/60 Hz, Class 2
Power5 VA (consumption), 40 VA (input)
Inputs9 configurable analog inputs (outside temperature / return / supply / zone / water supply / dry contact for clogged filter / schedule override / proof of fan / alarm, room setpoint, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
MicroprocessorPIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
Dimensions5.39 in x 4.41 in x 2.25 in (137 mm x 112 mm x 57 mm)
Weight1.05 lbs (0.48 kg)
Environment-4 to 122 °F (-20 to 50 °C) Non-Condensing
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Documentation

Frequently Asked Questions

Does the PL-M2000-HP work with water source heat pumps?

Yes. It is configurable to run in air-to-air mode or water-to-air mode, and the input list includes a water supply temperature point.

How many compressor stages does the PL-M2000-HP control?

Up to 2 compressor stages, plus 2 stages of auxiliary heating.

Can the PL-M2000-HP act as a network master?

Yes. It acts as a master controller when connected to a Prolon network, and its FlexiZone system manages multiple zones by evaluating the average weighted demand of the zones using customized groups.

What input signal types does the PL-M2000-HP accept?

Each of the 9 analog inputs is individually configurable for thermistor, dry contact, 4-20mA, or 0-5 VDC.

What outputs does the PL-M2000-HP provide?

5 triac digital outputs rated 10-30 VAC source, 300 mA max with a resettable fuse, plus 3 analog outputs at 0-10 VDC, 40 mA max. Each of the eight outputs has a manual/off/auto switch.

Controller Type:
Heat Pump
Digital Outputs:
5
Analog Outputs:
3
Inputs:
9
Communication:
Modbus RTU (RS485)
Product Series: