null Skip to main content

ACI A/DLP-001-W-U-D-A-3 Multi-Range Differential Low Pressure Transmitter, 0-0.1 to 0-1 in WC (8 DIP-Selectable), 4-20mA/0-5V/0-10V Output, +/-0.5% FSO, with LCD, Pitot+DIN Rail, Made in USA

ACI

MSRP: $512.00
$186.20
(You save $325.80 )
(No reviews yet) Write a Review
SKU:
A/DLP-001-W-U-D-A-3
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Max Pressure1 in WC
Range Selection8 DIP-Switchable
DirectionUni or Bi (DIP)
Output Signal4-20mA / 0-5V / 0-10V
Accuracy+/-0.5% FSO
Display5-Digit LCD
AccessoriesPitot Tube + DIN Rail Clip Included
OriginMade in USA

The ACI A/DLP-001-W-U-D-A-3 is a differential low pressure transmitter built around a piezoresistive silicon sensing element, with up to 8 DIP-switch-selectable pressure ranges (0-0.1 to 0-1 in WC) configurable as either unidirectional or bidirectional. Field-selectable analog outputs include 4-20 mA, 0-5 VDC, and 0-10 VDC, all on the same unit. +/-0.5% FSO typical accuracy (including hysteresis, linearity, and repeatability at 71 F), front-cover pushbutton zero for in-place re-zeroing, and a flame-retardant polycarbonate enclosure with watertight cordgrip and hinged cover. This SKU ships with the 5-digit LCD display for on-board pressure readout, plus the A/PT-DLP pitot tube and A/DRC-DLP 35 mm DIN rail clip for duct-airflow installation out of the box.

Best for: building and duct static pressure monitoring, dirty-filter detection across air filters, airflow measurement with a pitot tube, fan and AHU process control, and other low-differential air pressure applications where the engineer wants to stock one transmitter SKU that can be DIP-switched to fit multiple ranges and output signals on the same job. The 8-range, 3-output flexibility is the headline value - one part number covers what would otherwise require multiple fixed-range transmitters.
5-YEAR
WARRANTY
Manufacturer-backed coverage. ACI DLP transmitters carry a 5-year limited warranty. ZOT Supply is an authorized ACI distributor; product ships factory-new from Middleton, Wisconsin with full manufacturer warranty intact and access to ACI technical support.

Key Features

8-Range, 3-Output DIP Configuration

Each unit supports up to 8 field-selectable pressure ranges via the SW3 DIP switch (0-0.1 to 0-1 in WC both unidirectional and bidirectional), plus 3 selectable output signals (4-20 mA, 0-5 VDC, 0-10 VDC) via SW1 and SW3. One part number covers many job requirements.

Piezoresistive Silicon Sensing

Solid-state silicon element with +/-0.5% FSO typical accuracy (hysteresis, linearity, and repeatability at 71 F included). Thermal effects are +/-0.067% FSO/F (0.12% FSO/C). Low warm-up drift, low long-term drift, stable across the 32-122 F compensated range.

On-Board 5-Digit LCD Display

Built-in LCD shows live differential pressure in either inches WC or pascals (DIP-selectable). Also displays AUTOZERO icon during zero-mode operation and OUT OF RANGE indicator when the sensed pressure exceeds the selected range - useful for commissioning and field troubleshooting.

Pitot Tube + DIN Rail Included

Ships with A/PT-DLP 7 in aluminum duct-static pitot tube (6.75 in insertion depth) and A/DRC-DLP 35 mm DIN rail clip. The pitot threads into the back of the enclosure for clean direct-mount duct airflow installation; the DIN rail clip lets the same unit panel-mount when needed.

Rugged Watertight Enclosure

Flame-retardant polycarbonate housing with UL94-5VA rating (more stringent than V-0). Watertight cordgrip pre-installed for the field wiring entry; the cordgrip can be removed to accept 1/2 in NPT conduit fittings instead. Hinged cover with integrated locking tab opens easily without tools.

Robust Overpressure Protection

Proof pressure: 270 in WC (67.2 kPa). Burst pressure: 415 in WC (103.3 kPa). The piezoresistive sensor tolerates significant overpressure events well above the maximum 1 in WC sensing range - protects against duct surge, fan startup transients, and accidental high-pressure mis-plumbing.

Selectable Range Options

This SKU offers 8 field-selectable ranges set via the internal DIP switch. Power must be off when changing the configuration:

Range TypeAvailable Settings
Unidirectional ranges (4)0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC
Bidirectional ranges (4)+/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC
Default (factory shipped)0-1 in WC (largest unidirectional)
Range selection methodDIP switch SW3 positions 1 and 2 (with position 5 = UNI or BI)

Technical Specifications

SpecificationValue
ModelA/DLP-001-W-U-D-A-3
Maximum Pressure (Sensor)1 in WC
Selectable Ranges (Unidirectional)0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC
Selectable Ranges (Bidirectional)+/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC
Direction ModeUnidirectional or Bidirectional, field-selectable via DIP switch SW3 position 5
Accuracy+/-0.5% FSO typical (includes hysteresis, linearity, repeatability at 71 F)
Output SignalsField-selectable: 4-20 mA (2-wire loop), 0-5 VDC (3-wire), or 0-10 VDC (3-wire)
Supply Voltage4-20 mA: 16-36 VDC (250 ohm load) or 22-36 VDC (500 ohm load) / 24 VAC +/-10%, 50/60 Hz; 0-5 VDC and 0-10 VDC: 15-36 VDC into >5K ohm load / 24 VAC +/-10%, 50/60 Hz
Supply Current4-20 mA: 24 mA minimum (0.83 VA); 0-5/0-10 VDC: 6 mA maximum (0.18 VA)
Output Limit4-20 mA: 21.5 mA max; 0-5 VDC: 5.25 V max; 0-10 VDC: 10.5 V max
Sensor TypePiezoresistive silicon
Compensated Temperature Range32 to 122 F (0 to 50 C)
Thermal Effects+/-0.067% FSO/F (0.12% FSO/C), referenced to 71 F
Response Time (0-100% FSO)4 seconds
Output Update Rate0.5 second intervals
Zero FunctionFront-panel SW2 pushbutton (3+ second press-and-hold)
Proof Pressure270 in WC (67.2 kPa)
Burst Pressure415 in WC (103.3 kPa)
Operating Temperature-4 to 185 F (-20 to 85 C)
Operating Humidity10 to 95% RH, non-condensing
Storage Temperature-22 to 185 F (-30 to 85 C)
MediaDry air or inert non-conductive gases
Display5-digit LCD display
Pressure Fitting MaterialNickel-plated brass or stainless steel
Tubing Size Accepted1/4 in OD x 0.170 in ID poly tubing
Wiring Connections3-position finger-pushbutton (spring) terminal blocks, accepts 16-24 AWG wires
Conduit EntryWatertight cordgrip installed (1/2 in NPT conduit accepted when cordgrip is removed)
Enclosure MaterialFlame-retardant polycarbonate, UL94-5VA flammability rating
Dimensions (L x W x D)5.56 x 4.35 x 2.25 in (141.29 x 110.43 x 57.24 mm)
Weight0.85 lb (0.385 kg)
Included AccessoriesA/PT-DLP pitot tube + A/DRC-DLP DIN rail clip
ApprovalsCE, REACH, RoHS2, WEEE
Country of OriginMade in USA - Middleton, Wisconsin
Warranty5-year limited
Manufacturer Part NumberA/DLP-001-W-U-D-A-3
This SKU already ships with the A/PT-DLP pitot tube and A/DRC-DLP DIN rail clip. Other compatible accessories: DLP-specific pitot and mounting (A/PT-DLP duct-static pitot tube, A/DRC-DLP 35 mm DIN rail clip). Generic pitot tubes (PT 3 in, PT 5.2 in, PT 7.5 in, PT 9.7 in averaging; SPT-3.5, SPT-8.0 static; VPT, VPT-8 velocity). Pickup ports for wall/room dP taps (A/SP-PUP stainless, A/R-PUP beige, A/R2-PUP white, A/O-PUP-H / A/O-PUP-V outdoor weatherproof).

Documentation

Frequently Asked Questions

What pressure ranges does the A/DLP-001-W-U-D-A-3 support?
This SKU supports 8 field-selectable ranges via the internal DIP switch. Unidirectional options: 0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC. Bidirectional options: +/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC. In bidirectional mode, 0 in WC corresponds to 50% of the output range (12 mA, 2.5 V, or 5 V depending on output selection). The maximum sensor capability for this part is 1 in WC.
How do I change the pressure range or output signal?
Power off the unit first - DIP switch changes are not recognized when power is on. Open the hinged front cover using the integrated locking tab. SW1 selects output mode (Vout for VDC, mA for 4-20 mA). SW3 has 5 positions: positions 1 and 2 select the pressure range; position 3 selects pascals or inches WC (LCD models only); position 4 selects 5 V or 10 V output (for VDC mode); position 5 selects unidirectional or bidirectional. Set all switches, then power on. Refer to the installation manual Figure 9 for the exact switch positions for each range.
How and when should I zero the transmitter?
Disconnect tubing from both H (high) and L (low) brass fittings so no pressure is applied to either port. Press and hold the SW2 ZERO button for 3+ seconds. On LCD-equipped models, the AUTOZERO icon will appear during zero mode and flash twice when the operation completes successfully. Re-zeroing is recommended before installation and periodically thereafter to compensate for stress-relaxation offset drift over time. Do NOT press zero with pressure applied - results will be incorrect.
What does the LCD display show?
The 5-digit LCD shows the live differential pressure reading in either inches of water column or pascals (selected by SW3 position 3 - power-cycle the unit after changing this switch for the change to take effect). The LCD also displays the AUTOZERO icon during a zero-mode operation, and an OUT OF RANGE indicator when sensed pressure exceeds the selected range setting. If OUT OF RANGE appears, power off the unit and verify pressure input with a separate gauge before changing the DIP switch settings.
What's included with the Pitot Tube + DIN Rail Clip version?
This SKU ships with the A/PT-DLP 7 inch aluminum duct-static pitot tube (6.75 in insertion depth) that threads directly into the back of the enclosure, plus the A/DRC-DLP 35 mm DIN rail clip that mounts to the rear of the enclosure with the two included screws. The two #8 x 3/4 in self-drilling mounting screws for panel installation are also included. If you don't need these accessories, the same range without them is available as A/DLP-001-W-U-D-A-0 at a lower price point.
How do I wire the transmitter?
Use 16-24 AWG twisted-pair or shielded cable. Each unit has 4-wire push-button spring terminal blocks: V+ (red), COM (black), VOUT (white), and IOUT (yellow). For 4-20 mA (2-wire VDC loop): use V+ and IOUT only. For 4-20 mA (3-wire VAC): use V+, COM, and IOUT. For 0-5 or 0-10 VDC: use V+, COM, and VOUT. Ground the shield only at the controller end to prevent ground loops. ACI recommends an isolated UL-listed Class 2 transformer when powering with 24 VAC. When sharing power with relay or solenoid coils, place an MOV, transorb, or flyback diode across each inductive load to prevent voltage spikes.
Brand:
ACI
Series:
DLP
Product Type:
Multi-Range Differential Low Pressure Transmitter
Pressure Range Family:
0-0.1 to 0-1 in WC
Maximum Pressure:
1 in WC
Selectable Ranges (Unidirectional):
0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC
Selectable Ranges (Bidirectional):
+/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC
Number of Selectable Ranges:
8 (4 uni + 4 bi)
Direction Mode:
Unidirectional or Bidirectional (DIP-switchable)
Output Signals:
4-20 mA / 0-5 VDC / 0-10 VDC (field-selectable)
Output Configuration:
DIP-switchable via SW1 and SW3
Accuracy:
+/-0.5% FSO typical
Display:
5-digit LCD display
Accessories Included:
Pitot Tube + DIN Rail Clip Included
Sensor Type:
Piezoresistive silicon
Compensated Temperature:
32 to 122 F, 0 to 50 C
Thermal Effects:
+/-0.067% FSO/F
Response Time:
4 seconds (0-100% FSO)
Output Update Rate:
0.5 second intervals
Zero Function:
Front-panel SW2 pushbutton (3+ second hold)
Proof Pressure:
270 in WC (67.2 kPa)
Burst Pressure:
415 in WC (103.3 kPa)
Operating Temperature:
-4 to 185 F, -20 to 85 C
Operating Humidity:
10 to 95% RH non-condensing
Storage Temperature:
-22 to 185 F, -30 to 85 C
Media:
Dry air and inert non-conductive gases
Pressure Fittings:
Nickel-plated brass or stainless steel
Tubing Accepted:
1/4 in OD x 0.170 in ID poly
Wiring:
3-position spring terminal blocks, 16-24 AWG
Conduit Entry:
Watertight cordgrip (1/2 in NPT compatible when cordgrip removed)
Enclosure:
Flame-retardant polycarbonate, UL94-5VA
Dimensions:
5.56 x 4.35 x 2.25 in
Weight:
0.85 lb (0.385 kg)
Approvals:
CE, REACH, RoHS2, WEEE
Country of Origin:
USA (Middleton, Wisconsin)
Warranty:
5-year limited

Videos Hide Videos Show Videos