ACI A/DLP-001-W-U-D-A-0 Multi-Range Differential Low Pressure Transmitter, 0-0.1 to 0-1 in WC (8 DIP-Selectable), 4-20mA/0-5V/0-10V Output, +/-0.5% FSO, with LCD, Made in USA

ACI

MSRP: $457.00
$166.20
(You save $290.80 )
(No reviews yet) Write a Review
SKU:
A/DLP-001-W-U-D-A-0
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Max Pressure1 in WC
Range Selection8 DIP-Switchable
DirectionUni or Bi (DIP)
Output Signal4-20mA / 0-5V / 0-10V
Accuracy+/-0.5% FSO
Display5-Digit LCD
AccessoriesNo Accessories
OriginMade in USA

The ACI A/DLP-001-W-U-D-A-0 is a differential low pressure transmitter built around a piezoresistive silicon sensing element, with up to 8 DIP-switch-selectable pressure ranges (0-0.1 to 0-1 in WC) configurable as either unidirectional or bidirectional. Field-selectable analog outputs include 4-20 mA, 0-5 VDC, and 0-10 VDC, all on the same unit. +/-0.5% FSO typical accuracy (including hysteresis, linearity, and repeatability at 71 F), front-cover pushbutton zero for in-place re-zeroing, and a flame-retardant polycarbonate enclosure with watertight cordgrip and hinged cover. This SKU includes the 5-digit LCD display for on-board pressure readout during commissioning, balancing, and troubleshooting - no handheld meter needed to verify what the transmitter is sensing.

Best for: building and duct static pressure monitoring, dirty-filter detection across air filters, airflow measurement with a pitot tube, fan and AHU process control, and other low-differential air pressure applications where the engineer wants to stock one transmitter SKU that can be DIP-switched to fit multiple ranges and output signals on the same job. The 8-range, 3-output flexibility is the headline value - one part number covers what would otherwise require multiple fixed-range transmitters.
5-YEAR
WARRANTY
Manufacturer-backed coverage. ACI DLP transmitters carry a 5-year limited warranty. ZOT Supply is an authorized ACI distributor; product ships factory-new from Middleton, Wisconsin with full manufacturer warranty intact and access to ACI technical support.

Key Features

8-Range, 3-Output DIP Configuration

Each unit supports up to 8 field-selectable pressure ranges via the SW3 DIP switch (0-0.1 to 0-1 in WC both unidirectional and bidirectional), plus 3 selectable output signals (4-20 mA, 0-5 VDC, 0-10 VDC) via SW1 and SW3. One part number covers many job requirements.

Piezoresistive Silicon Sensing

Solid-state silicon element with +/-0.5% FSO typical accuracy (hysteresis, linearity, and repeatability at 71 F included). Thermal effects are +/-0.067% FSO/F (0.12% FSO/C). Low warm-up drift, low long-term drift, stable across the 32-122 F compensated range.

On-Board 5-Digit LCD Display

Built-in LCD shows live differential pressure in either inches WC or pascals (DIP-selectable). Also displays AUTOZERO icon during zero-mode operation and OUT OF RANGE indicator when the sensed pressure exceeds the selected range - useful for commissioning and field troubleshooting.

Flexible Mounting Options

Direct panel-screw mount via two top/bottom flange holes (two #8 x 3/4 in self-drilling screws included), or add the optional A/DRC-DLP 35 mm DIN rail clip. The A/PT-DLP duct-static pitot tube can be added later for in-duct airflow measurement.

Rugged Watertight Enclosure

Flame-retardant polycarbonate housing with UL94-5VA rating (more stringent than V-0). Watertight cordgrip pre-installed for the field wiring entry; the cordgrip can be removed to accept 1/2 in NPT conduit fittings instead. Hinged cover with integrated locking tab opens easily without tools.

Robust Overpressure Protection

Proof pressure: 270 in WC (67.2 kPa). Burst pressure: 415 in WC (103.3 kPa). The piezoresistive sensor tolerates significant overpressure events well above the maximum 1 in WC sensing range - protects against duct surge, fan startup transients, and accidental high-pressure mis-plumbing.

Selectable Range Options

This SKU offers 8 field-selectable ranges set via the internal DIP switch. Power must be off when changing the configuration:

Range TypeAvailable Settings
Unidirectional ranges (4)0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC
Bidirectional ranges (4)+/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC
Default (factory shipped)0-1 in WC (largest unidirectional)
Range selection methodDIP switch SW3 positions 1 and 2 (with position 5 = UNI or BI)

Technical Specifications

SpecificationValue
ModelA/DLP-001-W-U-D-A-0
Maximum Pressure (Sensor)1 in WC
Selectable Ranges (Unidirectional)0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC
Selectable Ranges (Bidirectional)+/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC
Direction ModeUnidirectional or Bidirectional, field-selectable via DIP switch SW3 position 5
Accuracy+/-0.5% FSO typical (includes hysteresis, linearity, repeatability at 71 F)
Output SignalsField-selectable: 4-20 mA (2-wire loop), 0-5 VDC (3-wire), or 0-10 VDC (3-wire)
Supply Voltage4-20 mA: 16-36 VDC (250 ohm load) or 22-36 VDC (500 ohm load) / 24 VAC +/-10%, 50/60 Hz; 0-5 VDC and 0-10 VDC: 15-36 VDC into >5K ohm load / 24 VAC +/-10%, 50/60 Hz
Supply Current4-20 mA: 24 mA minimum (0.83 VA); 0-5/0-10 VDC: 6 mA maximum (0.18 VA)
Output Limit4-20 mA: 21.5 mA max; 0-5 VDC: 5.25 V max; 0-10 VDC: 10.5 V max
Sensor TypePiezoresistive silicon
Compensated Temperature Range32 to 122 F (0 to 50 C)
Thermal Effects+/-0.067% FSO/F (0.12% FSO/C), referenced to 71 F
Response Time (0-100% FSO)4 seconds
Output Update Rate0.5 second intervals
Zero FunctionFront-panel SW2 pushbutton (3+ second press-and-hold)
Proof Pressure270 in WC (67.2 kPa)
Burst Pressure415 in WC (103.3 kPa)
Operating Temperature-4 to 185 F (-20 to 85 C)
Operating Humidity10 to 95% RH, non-condensing
Storage Temperature-22 to 185 F (-30 to 85 C)
MediaDry air or inert non-conductive gases
Display5-digit LCD display
Pressure Fitting MaterialNickel-plated brass or stainless steel
Tubing Size Accepted1/4 in OD x 0.170 in ID poly tubing
Wiring Connections3-position finger-pushbutton (spring) terminal blocks, accepts 16-24 AWG wires
Conduit EntryWatertight cordgrip installed (1/2 in NPT conduit accepted when cordgrip is removed)
Enclosure MaterialFlame-retardant polycarbonate, UL94-5VA flammability rating
Dimensions (L x W x D)5.56 x 4.35 x 2.25 in (141.29 x 110.43 x 57.24 mm)
Weight0.58 lb (0.263 kg)
Included AccessoriesNone (transmitter only)
ApprovalsCE, REACH, RoHS2, WEEE
Country of OriginMade in USA - Middleton, Wisconsin
Warranty5-year limited
Manufacturer Part NumberA/DLP-001-W-U-D-A-0
Compatible accessories: DLP-specific pitot and mounting (A/PT-DLP duct-static pitot tube, A/DRC-DLP 35 mm DIN rail clip). Generic pitot tubes (PT 3 in, PT 5.2 in, PT 7.5 in, PT 9.7 in averaging; SPT-3.5, SPT-8.0 static; VPT, VPT-8 velocity). Pickup ports for wall/room dP taps (A/SP-PUP stainless, A/R-PUP beige, A/R2-PUP white, A/O-PUP-H / A/O-PUP-V outdoor weatherproof).

Documentation

Frequently Asked Questions

What pressure ranges does the A/DLP-001-W-U-D-A-0 support?
This SKU supports 8 field-selectable ranges via the internal DIP switch. Unidirectional options: 0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC. Bidirectional options: +/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC. In bidirectional mode, 0 in WC corresponds to 50% of the output range (12 mA, 2.5 V, or 5 V depending on output selection). The maximum sensor capability for this part is 1 in WC.
How do I change the pressure range or output signal?
Power off the unit first - DIP switch changes are not recognized when power is on. Open the hinged front cover using the integrated locking tab. SW1 selects output mode (Vout for VDC, mA for 4-20 mA). SW3 has 5 positions: positions 1 and 2 select the pressure range; position 3 selects pascals or inches WC (LCD models only); position 4 selects 5 V or 10 V output (for VDC mode); position 5 selects unidirectional or bidirectional. Set all switches, then power on. Refer to the installation manual Figure 9 for the exact switch positions for each range.
How and when should I zero the transmitter?
Disconnect tubing from both H (high) and L (low) brass fittings so no pressure is applied to either port. Press and hold the SW2 ZERO button for 3+ seconds. On LCD-equipped models, the AUTOZERO icon will appear during zero mode and flash twice when the operation completes successfully. Re-zeroing is recommended before installation and periodically thereafter to compensate for stress-relaxation offset drift over time. Do NOT press zero with pressure applied - results will be incorrect.
What does the LCD display show?
The 5-digit LCD shows the live differential pressure reading in either inches of water column or pascals (selected by SW3 position 3 - power-cycle the unit after changing this switch for the change to take effect). The LCD also displays the AUTOZERO icon during a zero-mode operation, and an OUT OF RANGE indicator when sensed pressure exceeds the selected range setting. If OUT OF RANGE appears, power off the unit and verify pressure input with a separate gauge before changing the DIP switch settings.
How do I install the pitot tube and DIN rail clip?
Both are sold separately for this SKU. The A/PT-DLP pitot tube has a threaded end - slip the rubber washer over the threads (keeping it close to the threaded end), fasten the pitot into the threaded insert on the back of the enclosure, then press the washer against the enclosure to seal. Move the silicone tubing from the H barb fitting to the pitot tube barb (leaving the H fitting open to atmosphere). The A/DRC-DLP DIN rail clip screws to the back of the enclosure with the two included screws. If you want both pre-installed from the factory, order A/DLP-001-W-U-D-A-3 instead.
How do I wire the transmitter?
Use 16-24 AWG twisted-pair or shielded cable. Each unit has 4-wire push-button spring terminal blocks: V+ (red), COM (black), VOUT (white), and IOUT (yellow). For 4-20 mA (2-wire VDC loop): use V+ and IOUT only. For 4-20 mA (3-wire VAC): use V+, COM, and IOUT. For 0-5 or 0-10 VDC: use V+, COM, and VOUT. Ground the shield only at the controller end to prevent ground loops. ACI recommends an isolated UL-listed Class 2 transformer when powering with 24 VAC. When sharing power with relay or solenoid coils, place an MOV, transorb, or flyback diode across each inductive load to prevent voltage spikes.
Brand:
ACI
Series:
DLP
Product Type:
Multi-Range Differential Low Pressure Transmitter
Pressure Range Family:
0-0.1 to 0-1 in WC
Maximum Pressure:
1 in WC
Selectable Ranges (Unidirectional):
0-0.1 in WC, 0-0.2 in WC, 0-0.5 in WC, 0-1 in WC
Selectable Ranges (Bidirectional):
+/-0.1 in WC, +/-0.2 in WC, +/-0.5 in WC, +/-1 in WC
Number of Selectable Ranges:
8 (4 uni + 4 bi)
Direction Mode:
Unidirectional or Bidirectional (DIP-switchable)
Output Signals:
4-20 mA / 0-5 VDC / 0-10 VDC (field-selectable)
Output Configuration:
DIP-switchable via SW1 and SW3
Accuracy:
+/-0.5% FSO typical
Display:
5-digit LCD display
Accessories Included:
No Accessories
Sensor Type:
Piezoresistive silicon
Compensated Temperature:
32 to 122 F, 0 to 50 C
Thermal Effects:
+/-0.067% FSO/F
Response Time:
4 seconds (0-100% FSO)
Output Update Rate:
0.5 second intervals
Zero Function:
Front-panel SW2 pushbutton (3+ second hold)
Proof Pressure:
270 in WC (67.2 kPa)
Burst Pressure:
415 in WC (103.3 kPa)
Operating Temperature:
-4 to 185 F, -20 to 85 C
Operating Humidity:
10 to 95% RH non-condensing
Storage Temperature:
-22 to 185 F, -30 to 85 C
Media:
Dry air and inert non-conductive gases
Pressure Fittings:
Nickel-plated brass or stainless steel
Tubing Accepted:
1/4 in OD x 0.170 in ID poly
Wiring:
3-position spring terminal blocks, 16-24 AWG
Conduit Entry:
Watertight cordgrip (1/2 in NPT compatible when cordgrip removed)
Enclosure:
Flame-retardant polycarbonate, UL94-5VA
Dimensions:
5.56 x 4.35 x 2.25 in
Weight:
0.58 lb (0.263 kg)
Approvals:
CE, REACH, RoHS2, WEEE
Country of Origin:
USA (Middleton, Wisconsin)
Warranty:
5-year limited