null Skip to main content

Functional Devices MOD2-07-33MV : Rogowski Coil CT Integrator, 2-Phase, 70 mV to 333 mV, DIN Rail Mount

Functional Devices

MSRP: $811.90
Your Price:  $405.95
(You save $405.95 )
(No reviews yet) Write a Review
SKU:
MOD2-07-33MV
Condition:
New
Availability:
Ships 3-5 Days
Adding to cart… The item has been added

Quick Facts

Function

Rogowski CT integrator

Phases

2

Input / Output

70 mV AC in, 0.333 Vac out

Accuracy

0.5% typical

Power

12 Vdc @ 1.2 A or 24 Vdc @ 0.6 A

Warranty

10 years

Functional Devices MOD2-07-33MV Rogowski Coil CT Integrator

The Functional Devices MOD2-07-33MV is a DIN-rail mounted, two-phase Rogowski coil CT integrator that converts the 70 mV output of ROPE-series flexible current transformers to the 0.333 Vac analog standard accepted by 333 mV input power meters such as the RIB BACnet family. One MOD2-07-33MV conditions 2 ROPE coils at 0.5% typical accuracy, completing the signal chain for revenue-grade metering on 4,000 to 10,000 A services.

Wiring follows the application drawing in the MOD-series datasheet: the ROPE coil's red and black leads land on the integrator input (Red-Hi, Black-Low), the 0.333 V output feeds the meter's CT terminals, and the module is powered from a 12 Vdc supply at 1.2 A or a 24 Vdc supply at 0.6 A. Linearity is 10%-120% across a 40-400 Hz range, indoors. The MOD series is designed and made in the USA with global materials and carries the Functional Devices 10-year warranty.

Specifications verified against the Functional Devices MOD Series datasheet (rev. 2025.08.12) and Current Transformers family guide C2777D (rev. 2026.03.25).

Best For

  • Completing a ROPE Rogowski coil installation on two-phase service entrances and switchgear
  • Feeding RIB BACnet power meters from 4,000-10,000 A mains that only a flexible coil can enclose
  • DIN-rail control panels where the CT signal conditioning mounts beside the metering hardware
  • Revenue-grade measurement chains requiring 0.5% integrator accuracy
10-YEAR WARRANTY

Every Functional Devices RIB product, including the MOD2-07-33MV, is backed by the company's 10-year warranty — confidence and peace of mind in every box.

AUTHORIZED DISTRIBUTOR

ZOT Supply is an authorized Functional Devices distributor. Every MOD2-07-33MV ships as genuine, factory-warranted product with full manufacturer support.

Key Features

Converts 2 ROPE Coils to 333 mV

Accepts the 70 mV AC output of 2 ROPE-series Rogowski coils and integrates it to a clean 0.333 Vac full-scale signal, the standard input for the RIBPM413-BC meter family and other Listed 333 mV meters.

0.5% Typical Accuracy

Adds only 0.5% typical error with 10%-120% linearity across 40-400 Hz, preserving the revenue-grade quality of the ROPE coil measurement.

DIN Rail Mount

Snaps onto standard DIN rail inside the metering or control enclosure; the 2-phase module measures 3.54 in x 1.42 in x 1.11 in.

Flexible DC Power

Runs from either a 12 Vdc supply at 1.2 A or a 24 Vdc supply at 0.6 A, fitting whatever control power is already in the panel.

Simple Polarized Wiring

Red-Hi, Black-Low input terminals mirror the ROPE coil leads, and the datasheet's application drawing shows the full coil-to-integrator-to-meter chain.

ETL Listed

ETL Listed with CE and RoHS marks, designed and made in the USA with global materials, backed by the 10-year warranty.

Technical Specifications

Functional Devices MOD2-07-33MV Specifications
Selection
FunctionRogowski coil CT integrator (for use with ROPE series)
Phases2
Ratio70mV/333mV
Electrical
Input70 mV AC, 60 Hz (ROPE-series Rogowski coil output)
Output0.333 Vac full scale
Accuracy0.5% (typical)
Linearity10%-120%
Frequency Range40-400 Hz
PolarityRed-Hi, Black-Low
Power Supply12 Vdc @ 1.2 A or 24 Vdc @ 0.6 A
Mechanical and Environment
MountingDIN rail
Dimensions3.54 in x 1.42 in x 1.11 in
EnvironmentIndoor use only; 5 to 149 °F (-15 to 65 °C); 90% RH
Approvals
ApprovalsETL Listed, CE, RoHS

Documentation

PDF
Functional Devices MOD Series Datasheet

Specifications, selection guide, and ROPE application drawing, rev. 2025.08.12

PDF
Functional Devices ROPE Series Datasheet

Companion Rogowski coil CTs, rev. 2025.09.25

PDF
Current Transformers Family Guide

C2777D — full split-core, solid-core, Rogowski, and MOD-series lineup

Related Products

Functional Devices RIBPM413-BC

Open-board BACnet MS/TP power meter

Functional Devices RIBPM413-BC-KIT

Prewired kit with disconnect and fuses

Functional Devices RIBTPM413-BC

Meter in NEMA 1 housing with NPT hub

Frequently Asked Questions

What does a Rogowski coil integrator do?

A Rogowski coil outputs a low-level signal proportional to the rate of change of current rather than the current itself, so it must be electronically integrated before a standard meter can read it. The MOD2-07-33MV performs that integration and scales the result to 0.333 Vac full scale, the input the RIB power meters accept.

Which ROPE coils and meters does it work with?

Per the datasheet it is for use with any ROPE-series coil (4,000 A through 10,000 A), and its 0.333 Vac output feeds the RIBPM413-BC, RIBPM413-BC-KIT, and RIBTPM413-BC, or any other meter that accepts Listed 333 mV current transformers.

How many coils does the MOD2-07-33MV handle?

It is the 2-phase model, conditioning 2 ROPE coils. Use MOD1-07-33MV for one phase, MOD2-07-33MV for two, or MOD3-07-33MV for a full three-phase service.

What power supply does it need?

A DC control-power source: 12 Vdc at 1.2 A or 24 Vdc at 0.6 A, wired per the application drawing in the MOD series datasheet.

Can I install it outdoors?

No. The datasheet rates it for indoor use only, 5 to 149 deg F (-15 to 65 deg C) at up to 90% relative humidity.

Input Signal:
70 mV
Output Signal:
333 mV
Mounting:
DIN Rail
Power Supply:
12 or 24 Vdc
Compatible With:
ROPE Series