Functional Devices RIBTPM413-BC : Power Monitor 120-277V 3-phase BACnet compatible
SPECIFICATIONS
Power Meter - RIBPM413-BC:
Power Input Rating: Powered from Line 1 to Neutral, 120-277 Vac, < 2 VA
Headers: Pluggable screw terminal, accepts up to 12 AWG stranded copper wire
Frequency: 50/60 Hz
Operating Temperature: -4 to 158 °F
Storage Temperature: -40 to 185 °F
Humidity: 5 to 95% (noncondensing)
Altitude: Up to 2,000 m
Remote LED:
Green = Rx
Amber = Tx
Status LED: See Bulletin B2646
Dimensions: 2.75" x 4.5" x 0.85" with headers installed
Track Mount: MT212-4 mounting track provided
Approvals:CE, UL Listed, UL 61010-1 and UL 61010-2-30, C-UL, RoHS, FCC Part 15 Class B
Network Media: 18-22 AWG, 2-Core, shielded twisted pair
Network Termination: For End of Line (EOL) device, use 120 Ω Resistor. See Bulletin B2646 for details
Polarity: Network is polarity sensitive
Baud Rate: 9600, 19200, 38400, 57600, 76800, 115200; set via BACnet®
Metered Circuit:
Voltage Range: 120 - 277 Vac L-N (CAT III); 1P 2/3W, 3P 4W
Voltage Overload: 1.1 x Voltage Range
Voltage Burden: < 0.1 VA @ 277 Vac
Frequency Range: 45 - 65 Hz
Current Transformer: 333 mV Output (sold separately)
Current Overload: 1.2 x CT Output
Power Overload: 1.2 x Voltage Range x CT Output
Measurement Accuracy:
Voltage: 0.5%, < 0.2% typical from 80-120%
Current: 0.5%, < 0.2% typical from 10-120%
Power: 0.5%, < 0.2% typical from 10-120%
Power Factor: 0.5% between 0.5 and 1.0
Accessories:
CT-25A-333, CT-50A-333, CT-100A-333
Notes:
-See Bulletin B2646 for installation instructions
- Bi-directional for NET metering
- Order NEMA 4 housing by adding “-N4" to end of model number. (RIBTPM413-BC-N4)
- Order with grey lid by adding “-GY" to end of model number. (RIBTPM413-BC-GY)
- Order NEMA 4 housing with grey lid by adding “-N4-GY"to end of model number. (RIBTPM413-BC-N4-GY)
BACnet® Details:
-Device ID Default: 277050
-MAC Address Default: 50
-Baud Rate Default: 38400
-CT-Ratings (AV-8005) must be updated with the current rating of the CTs used with the device.
-See Bulletin B2646 for further details
|
- Supported Protocols:
- BACnet MS/TP
- Meter Type:
- Single Circuit
- Mounting:
- Track Mount
- Current Channels:
- 3