null Skip to main content

Prolon PL-C1050-HPS : Standalone Heat Pump Controller, 4 Digital Outputs, 1 Analog Output, 4 Configurable Inputs, Modbus RTU (RS485)

Prolon

Your Price:  $715.72
(No reviews yet) Write a Review
SKU:
PL-C1050-HPS
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
ApplicationStandalone Heat Pump Controller
Digital Outputs4 triac
Analog Output1
Inputs4 configurable
CommunicationModbus RTU (RS485)
Supply24 VAC, Class 2
The Prolon PL-C1050-HPS is a standalone Modbus RTU heat pump controller for unitary air-to-air and water-to-air systems driven from a single space temperature sensor.

Specifications on this page are taken from the Prolon Standalone Heatpump Controller datasheet, REV 7.3.0 / PL-DATA-C1050HPS-C/F-EN.

The PL-C1050-HPS is the standalone version of the C1050 heat pump controller, built for unitary systems that serve one space from a single space temperature sensor.

It works in air-to-air or water-to-air mode, controls up to two compressor stages or two stages of auxiliary heating, and includes economizer, preheating and emergency auxiliary heating sequences.

All four inputs are configurable and can be assigned to outside, return, supply or water intake temperature, night setback, proof of fan or alarm. It runs stand-alone or on a Prolon network of up to 127 nodes.

Best For

  • Unitary heat pump systems running from a single space temperature sensor
  • Air-to-air and water-to-air units
  • Up to 2 compressor stages or 2 stage auxiliary heating

Key Features

Built for single-zone unitary systems

Designed for unitary systems using a single space temperature sensor.

Air-to-air or water-to-air

Works in Air-To-Air mode or Water-To-Air mode, selected in configuration.

Two compressor or auxiliary heat stages

Controls up to 2 compressor stages or 2 stage auxiliary heating stages.

Four configurable inputs

4 configurable inputs with selectable functions: outside temp, return temp, supply temp, water intake temp, night setback, proof of fan or alarm.

Configurable protection limits

Built-in protection sequences with configurable temperature limits and minimum delays.

Protected outputs

All 4 digital outputs and the analog output are protected by resettable fuses.

Technical Specifications

SpecificationPL-C1050-HPS Value
Supply24 VAC ±10%, 50/60 Hz, Class 2
Power2 VA (consumption), 32 VA (input)
Inputs
  • 4 configurable inputs with selectable functions: outside temperature, return temperature, supply temperature, water intake temperature, night setback, proof of fan, alarm
Digital Outputs4 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Output1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
MicroprocessorPIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max)
Dimensions6.2 in x 5.2 in x 2.5 in (157 mm x 132 mm x 64 mm)
Weight0.85 lbs (0.39 kg)
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Documentation

Frequently Asked Questions

Does the PL-C1050-HPS support BACnet?
No. The HPS is Modbus RTU (RS485) only, up to 127 nodes. For native BACnet MS/TP on a heat pump, order the PL-C1050-HP.
How is the HPS different from the HP?
The HPS is built for unitary systems running from a single space temperature sensor. The HP adds FlexiZone multi-zone management, master-controller operation and BACnet MS/TP.
Does it work on water source heat pumps?
Yes. It works in Air-To-Air mode or Water-To-Air mode, selected in configuration.
How many stages does it control?
Up to 2 compressor stages or 2 stage auxiliary heating stages.
Can it be networked?
Yes. It operates stand-alone or networked with up to 127 nodes.
Controller Type:
Heat Pump
Digital Outputs:
4
Analog Outputs:
1
Configurable Inputs:
4
Communication:
Modbus RTU (RS485)